Installation (Applicable to all Models)Figure 6Piping connections for split system fan coil units - Downflow models<strong>Liebert</strong> <strong>iCOM</strong>ControlPIPING OUTLET LOCATIONS(See Cabinet and FloorPlanning Dimensional Datafor Piping Opening Sizes.)Condensate Drain3/4" FPTField pitch a minimumof 1/8" (3.2mm) per ft. (305mm).The drainline must comply<strong>with</strong> all applicable codes.HumidifierWater Supply Line1/4" OD CULiquid Refrigerant Line#6 Quick Connect on Models BF036E/BF035E1/2" OD CU on Models BF060E/BF059ESuction Refrigerant Line#11 Quick Connect on Models BF036E/BF035E1-1/8" OD CU on Models BF060E/BF059EHot Water Return5/8" OD CU (optional)Hot Water Supply5/8" OD CU (optional)DPN000376Rev. 0112