Figure 10 Piping connections for chilled water self-contained units - Downflow modelsInstallation (Applicable to all Models)<strong>Liebert</strong> <strong>iCOM</strong>ControlPIPING OUTLET LOCATIONS(See Cabinet and Floor PlanningDimensional Data for PipingOpening Sizes.)Condensate Drain3/4" FPTField pitch a minimumof 1/8" (3.2mm) per ft. (305mm).The drain line must comply<strong>with</strong> all applicable codes.Humidifier Water Supply Line1/4" OD CUChilled Water Supply Line1-1/8" OD CUChilled Water Return Line1-1/8" OD CUHot Water Return5/8" OD CU (optional)Hot Water Supply5/8" OD CU (optional)DPN000371Rev. 0116