Figure 11 Piping connections for chilled water self-contained units - Upflow modelsInstallation (Applicable to all Models)Piping outlet locations throughthe plenum are the same as the unit.See below for descriptions andconnection sizes.Humidifier Water Supply Line1/4" OD CUChilled Water Supply Line1-1/8" OD CUCondensate Pump Line1/2" OD CU; used only if optionalcondensate pump is ordered.Hot Water Return5/8" OD CU (optional)Chilled Water Return Line1-1/8" OD CUHot Water Supply5/8" OD CU (optional)<strong>iCOM</strong> ControlPanelCondensate Drain 3/4" FPTField-pitch a min. of 1/8" (3.2mm) per ft. (305mm). Units <strong>with</strong>outa condensate pump have a factory-supplied trap in the unit, so afield trap should not be added. Units <strong>with</strong> a condensate pump willrequire a field-supplied trap downstream from the pump. Thedrain line must comply <strong>with</strong> all applicable codes. (If condensatepump is ordered, piping is out top of unit).PIPING OUTLET LOCATIONS(See Cabinet and Floor PlanningDimensional Data for PipingOpening Sizes.)DPN000370Rev. 0117