9.9 Alteration of Existing Shell Penetrations<br />

9.9.1 Altered details must comply with <strong>API</strong>-650.<br />

9.9.2 New bottom installation (above old bottom) and using the<br />

slotted“ method through the shell may not now meet spacing requirements.<br />

Options for alternate compliance include the following three (3) items:<br />

9.9.2.1 Existing reinforcement plate may be "trimmed" to increase the spacing<br />

between the welds, provided the modification still meets <strong>API</strong>-650.<br />

9.9.2.2 Remove existing reinforcement and install a new pad.<br />

"Tombstone“ shapes are acceptable. The existing upper half of he<br />

reinforcement plate my be used, with a new lower plate installed. A telltale<br />

hole must be installed in the new plate.<br />

9.9.2.3 The existing penetration (nozzle and pad) may be removed<br />

and the entire assembly relocated to the correct elevation.<br />

Charlie Chong/ Fion Zhang