11.3 Cathodic Protection Surveys<br />

11.3.1.2 Annual cathodic protection surveys are recommended to<br />

ensure the effectiveness of cathodic protection.<br />

11.3.2 Inspection, Testing, and Maintenance of Cathodic<br />

Protection Facilities<br />

11.3.2.2 All sources of impressed current should be checked at<br />

intervals not exceeding two months unless specified otherwise by<br />

regulation.<br />

11.3.2.3 All impressed current protective facilities should be<br />

inspected annually as part of a preventive maintenance program to<br />

minimize in-service failure. Inspections should include a check of the<br />

general condition, including electrical shorts, ground connections,<br />

rectifier meter accuracy, efficiency, and circuit resistance.<br />

Annual<br />

Bi-monthly<br />

Annual<br />