Q7. What primary factor determines the interval between internal and<br />

external inspections?<br />

a. Jurisdictional regulations<br />

b. Tank service history, unless special reasons indicate an earlier inspection<br />

is required.<br />

c. Known (or suspected) corrosion activity of product.<br />

d. Change of service to a product with a specific gravity 10% higher than prior<br />

stored product.<br />

ANS: B<br />

Q8. What is the minimum dimension for a shell ring replacement piece or<br />

segment?<br />

a. The actual area requiring renewal, plus 6" on all four surrounding<br />

sides.<br />

b. 12" or 12 times the "t" of the replacement plate, whichever is<br />

greater.<br />

c. 10% of the individual ring segment involved.<br />

d. 20% of the individual ring segment involved.<br />

ANS: B<br />