12.1.2 Shell Penetrations<br />

12.1.2.1 UT lamination check required for:<br />

a. Adding reinforcement plate to an unreinforced penetration.<br />

b. Installing a hot-tap connection.<br />

12.1.2.2 Cavities from gouging or grinding to remove reinforcement<br />

pad welds require either a magnetic particle or liquid penetrant test.<br />

12.1.2.3 Completed welds attaching nozzle to shell or pad to shell and nozzle<br />

neck shall be examined by a magnetic particle or liquid penetrate test.<br />

Consideration should be given for extra NDE on hot taps.<br />

12.1.2.4 Complete welds in stress relieved components require magnetic<br />

particle or liquid penetrate testing (after stress relief, but before hydrostatic<br />

test).<br />

Charlie Chong/ Fion Zhang