ENGLISH<br />
Attention: to use the panel <strong>ED</strong> 3 M <strong>HS</strong> choose the dimensions of the hydraulic system so as to limit the maximum<br />
number of starts per hour to 20 (1 start every 3 minutes).<br />
8.2 Characteristics and interpretation of the wiring diagram references.<br />
The control panel is self-protected and protects the electropump against overloads, short circuits and overtemperatures,<br />
with manual reset. It comes complete with terminals for connecting the motor and the control floats.<br />
Complete with terminals to allow the use of an alarm float and with terminals (without potential) for remote feeding of<br />
an acoustic or luminous alarm. Provided with a button for manual operation of the electropump.<br />
<strong>ED</strong> 3 M<strong>HS</strong>: provided with an automatic device for increasing the static torque time on starting, set by the manufacturer<br />
at 2 seconds (NB do not set at over 4 seconds).<br />
The internal transformer is supplied complete with a self-resetting protection against overloads or<br />
short circuits, which manually cuts out the supply voltage for 3 minutes.<br />
Ref. Function (references on the enclosed wiring diagrams booklet)<br />
Automatic magnetothermal switch, for protection of the P1 motor supply line against overloads and short<br />
circuits, with manual reset.<br />
Supply line insulating switch.<br />
Button for manual operation of the electropump as long as it is pressed.<br />
Timer for regulating the strong static torque time. Possibility of regulation from 0.5 to 4 sec. set by the<br />
manufacturer during calibration at 2 sec. (only for <strong>ED</strong> 3 M <strong>HS</strong> ).<br />
Green warning light indicating that the electropump is being fed.<br />
QM1<br />
QS1<br />
SB1<br />
KT1<br />
HL3<br />
A<br />
1 - 2<br />
A + B<br />
1 - 2 __3 - 4<br />
P<br />
25 - 26<br />
Q<br />
31 - 32<br />
L1-N<br />
C-A-P<br />
K -K<br />
FU3<br />
FU4<br />
Connection terminals for the water minimum/maximum level control float.<br />
Contact characteristics: 24V a.c. 37mA<br />
Connection terminals for the minimum level (A - Stop level) maximum level (B - start level) control floats.<br />
Contact characteristics: 24V a.c. 37Ma<br />
Controls A, B do not require connection to as they are connected to the<br />
PELV safety circuit (CEI EN 60204-1).<br />
Connection terminals for the alarm float. Contact characteristics: � 8 Amp; ��250V.<br />
Any intervention of the panel protections do not exclude the float function.<br />
Connection terminals for the remote alarm for indicating intervention of the alarm float.<br />
Contact characteristics: without potential, NO (normally open); � 8 Amp; ��250V.<br />
Electropump connection terminals for panels type <strong>ED</strong> 1,3 M.<br />
Scrupulously respect the required correspondence.<br />
Electropump connection terminals for panels type <strong>ED</strong> 3 M – <strong>ED</strong> 3 M <strong>HS</strong>.<br />
Scrupulously respect the required correspondence.<br />
Connection of motor thermal protector.<br />
ATTENTION! For pumps with KK thermal protector, please remove the<br />
connector for KK clamps of the control panel and connect them with<br />
protection cables which are present on the pump cable (pag. 96).<br />
Fuses for protecting the transformer against incorrect connection of the motor leads (0.2A)<br />
The panel remains live even after intervention of the protection device which interrupts operation. (only for <strong>ED</strong> 3 M,<br />
<strong>ED</strong> 3 M <strong>HS</strong>)<br />
Disconnect the power before maintenance.<br />
Fuses for protecting the relay KA1 against incorrect connection of the motor leads (0.2A)<br />
The panel remains live even after intervention of the protection device which interrupts operation. (only for <strong>ED</strong> 3 M,<br />
<strong>ED</strong> 3 M <strong>HS</strong>)<br />
Disconnect the power before maintenance.<br />
14 Spare fuses for FU3 or FU4 (0,2A).<br />