ENGLISH<br />
Connection terminals for the alarm float. Contact characteristics: � 8 Amp; ��250V<br />
Any intervention of the panel protections do not exclude the float function.<br />
Connection terminals for the remote alarm for indicating intervention of the alarm float.<br />
Contact characteristics: without potential, NO (normally open); � 8 Amp; ��250V.<br />
Electropump P1 connection leads for panels type <strong>ED</strong> 1 T – <strong>ED</strong> 1,5 T.<br />
Scrupulously respect the required correspondence.<br />
Electropump P1 connection leads for panels type <strong>ED</strong> 2,5 T, <strong>ED</strong> 4 T, <strong>ED</strong> 7,5 T, <strong>ED</strong> 8 T.<br />
Scrupulously respect the required correspondence.<br />
Electropump P1 connection leads for panels type <strong>ED</strong> 15 T SD, <strong>ED</strong> 20 T SD.<br />
Scrupulously respect the required correspondence.<br />
Connection of motor thermal protector.<br />
ATTENTION! For pumps with KK thermal protector, please remove the<br />
connector for KK clamps of the control panel and connect them with<br />
protection cables which are present on the pump cable (pag. 96).<br />
Fuses for protecting the transformer against incorrect connection of the motor leads (0.2A)<br />
The panel remains live even after intervention of the protection device which interrupts operation. (only for <strong>ED</strong> 2,5 T)<br />
Disconnect the power before maintenance.<br />
Fuses for protecting the relay KA1 against incorrect connection of the motor leads (0.2A)<br />
The panel remains live even after intervention of the protection device which interrupts operation. (only for <strong>ED</strong> 2,5 T)<br />
Disconnect the power before maintenance.<br />
14 Spare fuses for FU3 or FU4 (0,2A).<br />
9.3 Electrical connections<br />
9.3.1 Before connecting the power cables to terminals L1 - L2 - L3 of the insulating switch, ensure that the main<br />
switch on the power distribution panel is in OFF position (O), and that no one can switch on the power<br />
accidentally.<br />
9.3.2 Scrupulously observe all the regulations in force concerning safety and accident prevention.<br />
9.3.3<br />
Ensure that all the terminals are fully tightened, paying particular attention to the earth terminal.<br />
9.3.4 Connect the cables to the terminal board as indicated in the wiring diagrams given in the enclosed booklet.<br />
9.3.5 Check that all the connecting cables are in excellent condition, with the external sheathing unbroken.<br />
9.3.6 Check that the differential switch that protects the system is of the right size.<br />
Provide automatic protection of the supply line against short circuits by means<br />
of ACR fuses type “gG” according to the following table:<br />
PANEL MODEL <strong>ED</strong> 1 T <strong>ED</strong> 1,5 T <strong>ED</strong> 2,5 T <strong>ED</strong> 4 T <strong>ED</strong> 7,5 T <strong>ED</strong> 8 T<br />
FUSES 8 A 10 A 16 A 25 A 32 A 32 A<br />
PANEL MODEL <strong>ED</strong> 15 T SD <strong>ED</strong> 20 T SD <strong>ED</strong> 25 T SD <strong>ED</strong> 30 T SD<br />
FUSES 63 A 80 A 100 A 160 A<br />
9.3.7<br />
The apparatus must be correctly and safely earthed as required by the<br />
regulations in force.<br />
9.3.8 Depending on the type of installation, limit the maximum length of the power cable as follows:<br />
Panel model Max. line length ( m )<br />
( section 1.5 mm 2 Max. line length ( m )<br />
) ( section 2.5 mm 2 Max. line length ( m )<br />
)<br />
( section 4 mm 2 )<br />
<strong>ED</strong> 1 T 130 220 350<br />
<strong>ED</strong> 1,5 T 85 140 220<br />
<strong>ED</strong> 2,5 T 50 90 140<br />
29