H51308-v0A Manuale Istruzioni VTNC - Rhoss
H51308-v0A Manuale Istruzioni VTNC - Rhoss
H51308-v0A Manuale Istruzioni VTNC - Rhoss
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
SECTION II: INSTALLATION AND MAINTENANCE<br />
If there is still a gap between the frame and the false ceiling, it should<br />
be reduced by working on the brace nuts and lock nuts again:<br />
II.2.4 External renewal air and treated air outlet in<br />
an adjacent room (for models 60-85 only)<br />
The side openings made it possible to create a separate external<br />
renewal air inlet duct (5) and an air outlet duct in an adjacent room<br />
(6).<br />
Replace the grille:<br />
6<br />
5<br />
6<br />
5 External air inlet<br />
Air distribution in<br />
6<br />
adjacent room<br />
7 Polystyrene<br />
membrane<br />
7<br />
6<br />
5<br />
7<br />
7<br />
45°<br />
Replace the covers at the four corners of the frame, making sure that<br />
you secure the respective safety cords:<br />
II.2.3.4<br />
Checking the Correct Installation of the<br />
Frame-Grille Assembly (for all models)<br />
The frame must not show signs of deformity caused by excessive<br />
traction. It must be centred with respect to the false ceiling and, above<br />
all, it must guarantee an airtight seal between the air inlet and outlet.<br />
The figure shows the airtight seals (A-B), which prevent the air bypass<br />
(A) and treated air leakage (B) inside the false ceiling. After installing<br />
the assembly, check that the gap between the frame and the false<br />
ceiling is under 5 mm.<br />
Remove the external anti-condensation insulation, delimited by the<br />
punching, and remove the pre-cut sheet metal panels using a punch.<br />
Use a pencil to draw round the internal polystyrene (7), then cut it with a<br />
cutter, taking care not to damage the heat exchange coil behind it.<br />
II.2.4.1 Air Outlet in Adjacent Room (for models 60-<br />
85 only)<br />
An air outlet in an adjacent room requires the closure of at least the<br />
mouth corresponding to the duct using the specific kit KCB (blocking<br />
outlet mouths). An air recovery grille should be installed between the air<br />
conditioned room (where the unit is installed) and the adjacent room<br />
(near the floor if possible). Do not use the two pre-cut side openings on<br />
the unit at the same time.<br />
G<br />
W<br />
W D<br />
G<br />
W<br />
<strong>VTNC</strong><br />
D<br />
W Wall<br />
D Door<br />
G Grille<br />
W Wall<br />
D Door<br />
G Grille<br />
<strong>VTNC</strong><br />
max 5 mm<br />
G<br />
IMPORTANT!<br />
Do NOT use active carbon or electrostatic filter kits<br />
in the presence of ducts to the adjacent room.<br />
B<br />
A<br />
4-6 mm<br />
Use material suitable for operation at a constant temperature of 60 °C.<br />
The ducts may be made from flexible polyester (with a spiral steel core)<br />
or corrugated aluminium, clad externally with anti-condensation material<br />
(fibreglass of 12 ÷ 25 mm thick).<br />
Once installation is completed, the uninsulated surfaces of the ducts<br />
must be covered with anti-condensation insulation (for example,<br />
expanded neoprene of 6 mm thick).<br />
IMPORTANT!<br />
Failure to observe these instructions may cause<br />
dripping due to condensation. The manufacturer<br />
may not be held liable for any damage.<br />
41