4.4.3 Switching on of the fan<br />

BWA-<strong>KXE</strong>-Fetteinzelstehlager_englisch_02.doc<br />

Start-up<br />

It is only permitted to start-up the fan, if a sufficient<br />

acceleration torque is available, covering the<br />

complete range of acceleration up to the nominal<br />

speed.<br />

Start-up the fan with closed damper.<br />

In case the fan is of gastight design, check the housing, the<br />

shaft seal and the connections at inlet and discharge for<br />

tightness.<br />

Switch-on fan.<br />

Monitor the following values and document them:<br />

� During start-up<br />

- current consumption,<br />

- voltage,<br />

- vibrations (quiet running),<br />

- noises.<br />

� After start-up<br />

- current / voltage,<br />

- vibrations,<br />

- noises,<br />

- bearing temperatures<br />

- temperature increase at fan housing due to compression<br />

of handled gas.<br />

After start-up charge the fan.<br />

Monitor the following values of the fan and document them:<br />

- current consumption / voltage,<br />

- vibrations (quiet running),<br />

- noises,<br />

- bearing temperatures.<br />

The fan must be disconnected, when<br />

- specified values are exceeded<br />

(see chapter 1.2 Fan data sheet)<br />

- unacceptable vibration values or increased noise levels<br />

of the fan occur,<br />

- limit values are exceeded<br />

(see chapter 9.1.2 Limiting values vibrations)<br />

If the above mentioned malfunctions occur, contact<br />

the service specialists of the manufacturer.<br />