7.9 Maintenance schedule<br />

BWA-<strong>KXE</strong>-Fetteinzelstehlager_englisch_02.doc<br />

Maintenance<br />

Structural component Daily Weekly Quarterly Yearly<br />

impeller An inspection of the impeller must be carried out immediately, if<br />

� the permissible limiting values (see chapter 9.1.2 Limiting values vibrations) are<br />

exceeded,<br />

� changed impeller noises occur.<br />

Examine the impeller every 5,000 operating hours and check it for alteration (cracks,<br />

geometric alterations, balancing condition, wear and sticking material), but at least<br />

once a year.<br />

Check the impeller e.g. by non-destructive crack testing.<br />

Fans that are subject to high dynamical stresses are to be checked in accordance with the<br />

additional agreement (maintenance schedule) within the prescribed intervals.<br />

bearings<br />

An inspection of the bearings must be carried out immediately, if<br />

� the permissible limiting values (see chapter 9.1.2 Limiting values vibrations and<br />

9.1.3 Limiting values bearing temperatures) are exceeded,<br />

� changed running noises occur<br />

� unusual alterations of the lubricant occur.<br />

Re-lubrification intervals acc. to plate “Maintenance of the bearings” (see chapt.<br />

7.3.1.2 Lubrication intervals)<br />

shaft seal The shaft sealing rings have to be checked and exchanged if the sealing gas<br />

consumption or leakage increases. Exchange the shaft seal ring when the rings are<br />

worn or damaged. If the seal ring consists of more than one part, replace the full seal<br />

ring set.<br />

shaft earthing Check the correct functioning of the shaft earthing regularly and in dependence of<br />

the operating conditions and replace it, if required.<br />

condensate drain Drain the accumulated condense water in regular intervals or when required in a<br />

suitable drain receptacle and dispose of it in an environmentally compatible way.<br />

coupling If noise levels are changed abruptly and / or vibrations occur abruptly, the coupling<br />

must be checked and if required, it must be re-aligned or exchanged.<br />

motor pay attention to<br />

retighten screws, check motor, if<br />

running noises and<br />

check bearings required, exchange<br />

quiet running,<br />

bearings, observe<br />

remove sticking<br />

maintenance<br />

material (e.g. dust),<br />

instructions of<br />

if required<br />

motor manufacturer<br />

earthing motor<br />

clean inside, clean inside,<br />

terminal box<br />

tighten screws tighten screws<br />

connections for collect measuring check for functiona- check for functiona- check for functiona-<br />

monitoring devices and<br />

auxiliary equipment<br />

values<br />

litylitylity<br />

flexible connections check at regular intervals and – if check, if required, check, if required,<br />

required – after change of the processes. retighten screws retighten screws<br />

and if worn-out, and, if worn out,<br />

exchange flexible exchange flexible<br />

connections connections<br />

total fan pay attention to pay attention to check impeller, fan<br />

operational noises operational noises bearings and motor<br />

and quiet running and quiet running bearings, shaft<br />

seal, coupling and<br />

flexible connections<br />

for wear and, if<br />

required, repair or<br />

exchange them<br />

7.9