10.3 Measures in case of prolonged<br />
shutdown<br />
BWA-<strong>KXE</strong>-Fetteinzelstehlager_englisch_02.doc<br />
Fan shutdown<br />
When the fan is put out of operation for more than three<br />
months the following steps must be taken:<br />
- Drive motors and actuators<br />
If there are drains, please open them, drain the accumulated<br />
water and re-close the openings. Check the terminal<br />
box connections for tight screwing.<br />
- Protect all bright parts (especially fan shaft and coupling)<br />
from corrosion.<br />
- for single-bearing housings (fan shaft bearings)<br />
press in grease until fresh grease leaks out from the discharge<br />
bore and turn the shaft manually several times<br />
The grease type that was filled in and the relubrication<br />
grease type are indicated on the bearing plate (“Maintenance<br />
of bearings”.<br />
Do not use another grease type.<br />
Note on the time period of the fan shutdown:<br />
If the fan is taken out of operation for a period of<br />
more than twelve months, check the grease for deoiling<br />
or contamination (if condensate water intrudes<br />
in the grease, it will change its consistency). The<br />
grease has to be exchanged if it is de-oiled or contaminated.<br />
10.2