10.3 Measures in case of prolonged<br />

shutdown<br />

BWA-<strong>KXE</strong>-Fetteinzelstehlager_englisch_02.doc<br />

Fan shutdown<br />

When the fan is put out of operation for more than three<br />

months the following steps must be taken:<br />

- Drive motors and actuators<br />

If there are drains, please open them, drain the accumulated<br />

water and re-close the openings. Check the terminal<br />

box connections for tight screwing.<br />

- Protect all bright parts (especially fan shaft and coupling)<br />

from corrosion.<br />

- for single-bearing housings (fan shaft bearings)<br />

press in grease until fresh grease leaks out from the discharge<br />

bore and turn the shaft manually several times<br />

The grease type that was filled in and the relubrication<br />

grease type are indicated on the bearing plate (“Maintenance<br />

of bearings”.<br />

Do not use another grease type.<br />

Note on the time period of the fan shutdown:<br />

If the fan is taken out of operation for a period of<br />

more than twelve months, check the grease for deoiling<br />

or contamination (if condensate water intrudes<br />

in the grease, it will change its consistency). The<br />

grease has to be exchanged if it is de-oiled or contaminated.<br />