Indoor terminations for flexible, screened, rubber insulated cables 6 kV<br />
<strong>Cable</strong><br />
The termination is designed for 6 kV<br />
screened, flexible, rubber insulated cables<br />
with one or three earth cores.<br />
For example: NTSC, КГЭ, КГЭТ, Ogb,<br />
Ogc-G, CHCU, CBVU, EpN 64i65, EpN<br />
(BN) 64i74, EpN (BN) 76i78, EpN (BN)<br />
78/53.<br />
2 4<br />
Dimension L see table<br />
Design of termination<br />
Stress grading mastic is wrapped around<br />
the area of the screen cut. All cores are<br />
covered with non-tracking insulating<br />
tubing. The area between the end of the<br />
oversheath and the cores is sealed and<br />
protected by a 6- or 4-finger breakout. The<br />
cores remain flexible and can be bent like<br />
the cable.<br />
Terminations for other voltages or core lengths are available on request.<br />
Nominal voltage Cross section Ordering description by length<br />
Uo/U (kV) (mm2 )<br />
<strong>Cable</strong>s with 1 earth core<br />
L = 450 mm L = 1200 mm<br />
10/10– 70/ 70 EMKT 7A4IH2 EMKT 7A4IH5<br />
3,5/6<br />
95/95–185/185<br />
<strong>Cable</strong>s with 3 earth cores<br />
EMKT 7B4IH2 EMKT 7B4IH5<br />
25/10– 70/16 EMKT 7E6IH2 EMKT 7E6IH5<br />
95/16–185/35 EMKT 7F6IH2 EMKT 7F6IH5<br />
Note: One termination kit includes material for 3 phases.<br />
The core lengths can be reduced to the requirements at the place of installation, the minimum core length is 300 mm.<br />
Terminations for other voltages or core lengths are available on request.<br />