Termination for polymeric insulated Filter <strong>Cable</strong>s up to 150 kV D.C.<br />

<strong>Cable</strong><br />

The termination is designed for screened<br />

single core polymeric insulated cables<br />

with wire shield or metal sheath, cross<br />

section from 35 mm 2 to 95 mm 2 and<br />

diameter over insulation between 26 mm<br />

and 45 mm. <strong>Cable</strong>s designed for A.C.<br />

voltages 72,5, 111 or 150 kV usually meet<br />

the dimensional requirements.<br />

Dimensions L, D see table<br />

Ordering Description <strong>Cable</strong> dimensions Termination dimensions<br />

Cross Diameter of Diameter over Max. diameter Length Shed Number<br />

section conductor dielectric of cable diameter of sheds<br />

mm 2 mm mm mm mm mm<br />

FCEV-111 35–95 6–11,5 24–38 53 500 155 1<br />

FCEV-150 35–95 6–11,5 30–45 60 700 155 2<br />

Note: The termination FCEV is supplied as a single phase termination.<br />

Terminations for other cable types or dimensions are available on request.<br />

Overview of qualification tests:<br />

Type of test Passed requirements<br />

FCEV 111 FCEV 150<br />

Partial discharge test < 5 pC at 42 kV AC < 5 pC at 52 kV AC<br />

DC withstand test > 8 hours at – 200 kV > 8 hours at – 300 kV<br />

> 8 hours at + 200 kV > 8 hours at + 300 kV<br />

Impulse test > 200 times at – 240 kV > 50 times at – 325 kV<br />

(wave shape 1,2/50 µs, chopped) > 200 times at + 240 kV > 50 times at + 325 kV<br />

AC withstand test<br />

Detailed test reports are available on request.<br />

> 10 minutes at 80 kV > 10 minutes at 150 kV<br />

3 4<br />

Design of termination<br />

The cable is prepared in the same simple<br />

and easy way as for Raychem medium<br />

voltage terminations without sanding or<br />

pencilling. Based on the design of<br />

Raychem high voltage terminations, the<br />

filter cable termination consists of a<br />

staggered layer of stress control tubings<br />

and patches. A heat-shrinkable nontracking<br />

insulation tubing and shed are<br />

D<br />

L<br />

shrunk over the stress control system and<br />

ensure a reliable seal to the lug and the<br />

oversheath. A mechanical lug covering<br />

cross sections from 35 mm 2 to 95 mm 2 is<br />

supplied with the kit. The mechanical lug<br />

has a M10 thread on the top for easy<br />

connection to connecting busbars.<br />

The termination is supplied as a single<br />

phase termination. A solderless earth<br />

connection for cables with metal sheath is<br />

included in the termination kit.<br />

Testing and performance<br />

Neither national nor international<br />

specification exist for filter cable<br />

terminations. By understanding the<br />

specific operation requirements of a filter<br />

cable termination, Raychem developed a<br />

test specification and qualified the filter<br />

cable termination FCEV to these<br />

requirements. The overview of<br />

qualification tests is summarized in a<br />

table below.