Indoor termination for unscreened, 3-core polymeric insulated cables 6 kV and 10 kV<br />

<strong>Cable</strong><br />

The indoor termination is designed for 6 kV<br />

and 10 kV unscreened three core plastic<br />

insulated cables with armour or copper<br />

earth shield.<br />

For example: АПВГ, YAKYFtly, YKYFoY,<br />

YAKYFpy, AYKCY, CYKCY, NAYFGY, PP<br />

41-(A), PP 44-(A), PP45-(A), N(A)YFGY.<br />

2 6<br />

Dimension L see table<br />

Design of termination<br />

The cores are covered with non-tracking<br />

insulating tubing. The area between the<br />

end of the oversheath and the cores is<br />

sealed and protected by a non-tracking<br />

insulating breakout. Solderless earth<br />

connections can be ordered separately<br />

Nominal voltage Cross section Ordering description Dimension (mm)<br />

Uo/U (kV) (mm2 ) L<br />

EPKT 2041 450<br />

16– 50<br />

EPKT 2042<br />

EPKT 2043<br />

650<br />

800<br />

EPKT 2044 1200<br />

3,5/6 EPKT 2051 450<br />

and<br />

6/10<br />

70–120<br />

EPKT 2052<br />

EPKT 2053<br />

650<br />

800<br />

EPKT 2054 1200<br />

EPKT 2061 450<br />

150–240<br />

EPKT 2062<br />

EPKT 2063<br />

650<br />

800<br />

EPKT 2064 1200<br />

Note: One termination kit includes material for 3 phases.<br />

The core lengths can be reduced to the requirements at the place of installation, the minimum core length is 250 mm<br />

(450 mm for 10 kV).<br />

Solderless earth connection for cables with armour or copper tape shield<br />

Nominal voltage Cross section Ordering description<br />

Uo/U (kV) (mm2 )<br />

3,5/6<br />

16– 95<br />

120–300<br />

SMOE 60805<br />

SMOE 60873<br />

16 SMOE 60805<br />

6/10 25– 95 SMOE 60873<br />

120–300 SMOE 62176<br />

Note: The solderless earth connection kit must be ordered separately. It includes a roll spring and an earth lead.<br />