Indoor termination for unscreened, 3-core polymeric insulated cables 6 kV and 10 kV<br />
<strong>Cable</strong><br />
The indoor termination is designed for 6 kV<br />
and 10 kV unscreened three core plastic<br />
insulated cables with armour or copper<br />
earth shield.<br />
For example: АПВГ, YAKYFtly, YKYFoY,<br />
YAKYFpy, AYKCY, CYKCY, NAYFGY, PP<br />
41-(A), PP 44-(A), PP45-(A), N(A)YFGY.<br />
2 6<br />
Dimension L see table<br />
Design of termination<br />
The cores are covered with non-tracking<br />
insulating tubing. The area between the<br />
end of the oversheath and the cores is<br />
sealed and protected by a non-tracking<br />
insulating breakout. Solderless earth<br />
connections can be ordered separately<br />
Nominal voltage Cross section Ordering description Dimension (mm)<br />
Uo/U (kV) (mm2 ) L<br />
EPKT 2041 450<br />
16– 50<br />
EPKT 2042<br />
EPKT 2043<br />
650<br />
800<br />
EPKT 2044 1200<br />
3,5/6 EPKT 2051 450<br />
and<br />
6/10<br />
70–120<br />
EPKT 2052<br />
EPKT 2053<br />
650<br />
800<br />
EPKT 2054 1200<br />
EPKT 2061 450<br />
150–240<br />
EPKT 2062<br />
EPKT 2063<br />
650<br />
800<br />
EPKT 2064 1200<br />
Note: One termination kit includes material for 3 phases.<br />
The core lengths can be reduced to the requirements at the place of installation, the minimum core length is 250 mm<br />
(450 mm for 10 kV).<br />
Solderless earth connection for cables with armour or copper tape shield<br />
Nominal voltage Cross section Ordering description<br />
Uo/U (kV) (mm2 )<br />
3,5/6<br />
16– 95<br />
120–300<br />
SMOE 60805<br />
SMOE 60873<br />
16 SMOE 60805<br />
6/10 25– 95 SMOE 60873<br />
120–300 SMOE 62176<br />
Note: The solderless earth connection kit must be ordered separately. It includes a roll spring and an earth lead.<br />