21.03.2013 Views

Power Cable Accessories

Power Cable Accessories

Power Cable Accessories

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Joints for unscreened 3-core, polymeric insulated cables 6 kV and 10 kV<br />

<strong>Cable</strong><br />

The joints are designed for 3-core<br />

unscreened, polymeric insulated cables 6,<br />

10 kV with armour or common copper<br />

tape shield.<br />

For example: PP 41(A), PP 44(A), PP<br />

45(A), NAYFGY, AВВБ, AВВГ, AПВГ,<br />

YKYFtly, YKYFoy, YAKY, YKYFtly,<br />

YKYFoy, YAKY, YKY…, AYKCYDY,<br />

AYKCY, N(A)YBY, N(A)YGY.<br />

Joints including mechanical connectors<br />

7 2<br />

Design of transition joints<br />

to 1-core screened polymeric<br />

insulated cables<br />

The cores of the screened cable are<br />

covered with yellow, void filling mastic and<br />

heat-shrinkable stress control tubing. The<br />

conductors are jointed with a mechanical<br />

connector supplied with the joint. The<br />

connection area is covered with a stress<br />

control patch. A heat-shrinkable, dualwall,<br />

elastomeric tubing provides the<br />

correct thickness of insulation and the<br />

screening over the insulation. The<br />

shielding is rebuilt with copper mesh, and<br />

a solderless earth connection system<br />

provides the electrical connection. The<br />

outer sealing and protection is performed<br />

by an adhesive coated, thick-wall heatshrinkable<br />

tubing.<br />

Joints for cables with steel tape armour or common copper tape or wire shield<br />

Nominal voltage Cross section Ordering description Dimensions (mm)<br />

Uo/U (kV) (mm2 ) L D<br />

25– 50 POLJ-06/3x 25- 50 800 70<br />

3,5/6 70–120 POLJ-06/3x 70-120 900 90<br />

150–240 POLJ-06/3x150-240 1000 100<br />

25– 50 POLJ-06/3x 25- 50 800 70<br />

6/10 70–120 POLJ-06/3x 70-120 900 90<br />

150–240 POLJ-06/3x150-240 1000 100<br />

Transition joints for 3-core unscreened cables to 1-core screened cables including mechanical connectors<br />

Nominal voltage Cross section (mm 2 ) Ordering description Dimensions (mm)<br />

<strong>Cable</strong> type<br />

Uo/U (kV) 3-core 1-core* L D<br />

3,5/6<br />

Design of joints<br />

The connectors are insulated and sealed<br />

with thick-wall, heat-shrinkable tubings<br />

and mastic. The armour or copper tape<br />

shielding is rebuild with a wraparound<br />

metal case or with copper mesh. A<br />

solderless earth connection provides the<br />

electrical connection to the armour or<br />

copper shielding. The outer protection<br />

and sealing is performed by an adhesive<br />

coated heat-shrinkable tubing.<br />

Joints type POLJ are supplied with<br />

mechanical connectors, joints type EPKJ<br />

and SMOE are supplied without connectors.<br />

70–120 70–120 POLJ-12/1x 70-150-3U 1000 90<br />

150–240 150–240 POLJ-12/1x150-240-3U 1000 100<br />

6/10<br />

70–120<br />

120–240<br />

70–150<br />

150–240<br />

POLJ-12/1x 70-150-3U<br />

POLJ-12/1x150-240-3U<br />

1000<br />

1000<br />

90<br />

100<br />

* Application ranges apply for 10 and 20 kV cables<br />

Joints without connectors<br />

<strong>Cable</strong>s with armour<br />

Nominal voltage Cross section Ordering description for cables Dimensions (mm)<br />

Uo/U (kV) (mm2 ) with tape armour with wire armour L D<br />

3,5/6 16– 70 EPKJ 2079-J41 EPKJ 2079 800 75<br />

and 95–150 EPKJ 2080-J42 EPKJ 2080 1000 105<br />

6/10 185–300 EPKJ 2081-J43 EPKJ 2081 1200 135<br />

<strong>Cable</strong>s with common copper tape shield and without armour<br />

Nominal voltage Cross section Ordering description Dimensions (mm)<br />

Uo/U (kV) (mm2 ) L D<br />

25– 70 SMOE 62096 800 70<br />

3,5/6 95–185 SMOE 62095 1000 90<br />

240 SMOE 61302 1200 100