Power Cable Accessories
Power Cable Accessories
Power Cable Accessories
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Joints for unscreened 3-core, polymeric insulated cables 6 kV and 10 kV<br />
<strong>Cable</strong><br />
The joints are designed for 3-core<br />
unscreened, polymeric insulated cables 6,<br />
10 kV with armour or common copper<br />
tape shield.<br />
For example: PP 41(A), PP 44(A), PP<br />
45(A), NAYFGY, AВВБ, AВВГ, AПВГ,<br />
YKYFtly, YKYFoy, YAKY, YKYFtly,<br />
YKYFoy, YAKY, YKY…, AYKCYDY,<br />
AYKCY, N(A)YBY, N(A)YGY.<br />
Joints including mechanical connectors<br />
7 2<br />
Design of transition joints<br />
to 1-core screened polymeric<br />
insulated cables<br />
The cores of the screened cable are<br />
covered with yellow, void filling mastic and<br />
heat-shrinkable stress control tubing. The<br />
conductors are jointed with a mechanical<br />
connector supplied with the joint. The<br />
connection area is covered with a stress<br />
control patch. A heat-shrinkable, dualwall,<br />
elastomeric tubing provides the<br />
correct thickness of insulation and the<br />
screening over the insulation. The<br />
shielding is rebuilt with copper mesh, and<br />
a solderless earth connection system<br />
provides the electrical connection. The<br />
outer sealing and protection is performed<br />
by an adhesive coated, thick-wall heatshrinkable<br />
tubing.<br />
Joints for cables with steel tape armour or common copper tape or wire shield<br />
Nominal voltage Cross section Ordering description Dimensions (mm)<br />
Uo/U (kV) (mm2 ) L D<br />
25– 50 POLJ-06/3x 25- 50 800 70<br />
3,5/6 70–120 POLJ-06/3x 70-120 900 90<br />
150–240 POLJ-06/3x150-240 1000 100<br />
25– 50 POLJ-06/3x 25- 50 800 70<br />
6/10 70–120 POLJ-06/3x 70-120 900 90<br />
150–240 POLJ-06/3x150-240 1000 100<br />
Transition joints for 3-core unscreened cables to 1-core screened cables including mechanical connectors<br />
Nominal voltage Cross section (mm 2 ) Ordering description Dimensions (mm)<br />
<strong>Cable</strong> type<br />
Uo/U (kV) 3-core 1-core* L D<br />
3,5/6<br />
Design of joints<br />
The connectors are insulated and sealed<br />
with thick-wall, heat-shrinkable tubings<br />
and mastic. The armour or copper tape<br />
shielding is rebuild with a wraparound<br />
metal case or with copper mesh. A<br />
solderless earth connection provides the<br />
electrical connection to the armour or<br />
copper shielding. The outer protection<br />
and sealing is performed by an adhesive<br />
coated heat-shrinkable tubing.<br />
Joints type POLJ are supplied with<br />
mechanical connectors, joints type EPKJ<br />
and SMOE are supplied without connectors.<br />
70–120 70–120 POLJ-12/1x 70-150-3U 1000 90<br />
150–240 150–240 POLJ-12/1x150-240-3U 1000 100<br />
6/10<br />
70–120<br />
120–240<br />
70–150<br />
150–240<br />
POLJ-12/1x 70-150-3U<br />
POLJ-12/1x150-240-3U<br />
1000<br />
1000<br />
90<br />
100<br />
* Application ranges apply for 10 and 20 kV cables<br />
Joints without connectors<br />
<strong>Cable</strong>s with armour<br />
Nominal voltage Cross section Ordering description for cables Dimensions (mm)<br />
Uo/U (kV) (mm2 ) with tape armour with wire armour L D<br />
3,5/6 16– 70 EPKJ 2079-J41 EPKJ 2079 800 75<br />
and 95–150 EPKJ 2080-J42 EPKJ 2080 1000 105<br />
6/10 185–300 EPKJ 2081-J43 EPKJ 2081 1200 135<br />
<strong>Cable</strong>s with common copper tape shield and without armour<br />
Nominal voltage Cross section Ordering description Dimensions (mm)<br />
Uo/U (kV) (mm2 ) L D<br />
25– 70 SMOE 62096 800 70<br />
3,5/6 95–185 SMOE 62095 1000 90<br />
240 SMOE 61302 1200 100