Outdoor termination for unscreened, 3-core polymeric insulated cables<br />

6 kV and 10 kV<br />

<strong>Cable</strong><br />

The indoor termination is designed for 6 kV<br />

and 10 kV unscreened three core plastic<br />

insulated cables with armour or copper<br />

earth shield.<br />

For example: АПВГ , YAKYFtly, YKYFoy,<br />

YKYFtly, AYKCY, CYKCY, NAYFGY, PPO<br />

41-(A), PP 44-(A), PP45-(A), N(A)YFGY.<br />

Dimensions L, D see table<br />

Design of termination<br />

The cores are covered with non-tracking<br />

insulating tubing. The area between the<br />

end of the oversheath and the cores is<br />

sealed and protected by a non-tracking<br />

insulating breakout. Additional skirts are<br />

installed onto the tubing (see table).<br />

Nominal voltage Cross section Ordering description Dimensions (mm) No. of<br />

Uo/U (kV) (mm 2 ) L D skirts<br />

3,5/6<br />

16– 50<br />

EPKT 2292<br />

EPKT 2294<br />

650<br />

1200<br />

76<br />

76<br />

3 x 1<br />

3 x 1<br />

and<br />

6/10<br />

70–120<br />

EPKT 2302<br />

EPKT 2304<br />

650<br />

1200<br />

95<br />

95<br />

3 x 1<br />

3 x 1<br />

EPKT 2312 650 95 3 x 1<br />

150–240<br />

EPKT 2314 1200 95 3 x 1<br />

Note: One termination kit includes material for 3 phases. Longitudinally sealed cable lugs are to be used.<br />

The core lengths can be reduced to the requirements at the place of installation, the minimum core length is 450 mm.<br />

Solderless earth connection for cables with armour or copper tape shield<br />

Nominal voltage Cross section Ordering description<br />

Uo/U (kV) (mm2 )<br />

3,5/6<br />

16– 95<br />

120–300<br />

SMOE 60805<br />

SMOE 60873<br />

16 SMOE 60805<br />

6/10 25– 95 SMOE 60873<br />

120–300 SMOE 62176<br />

Note: The solderless earth connection kit must be ordered separately. It includes a roll spring and an earth lead.<br />