RSTI – Screened, separable T-connection system for gas-insulated switchgear with<br />

bushings according to EN 50181 type C (400/630A), 10 kV, 15 kV, 20 kV and 35 kV<br />

Raychem screened separable connectors<br />

are designed to connect single-core<br />

polymeric insulated cables to gasinsulated<br />

switchgear or other equipment<br />

with bushings according to EN 50181<br />

type C up to 42 kV. Connections can be<br />

made in a right-angle configuration, also<br />

for 2 or 3 cables in parallel, such<br />

configurations require mechanical fixing<br />

of each cable in the switchgear.<br />

For connections to 1250 A rated bushings<br />

with profile according to EN 505181 type<br />

C, parallel connections are possible with<br />

each RSTI rated for max. 630A.<br />

Made of a highly modified silicone rubber<br />

and protected with a thick wall moulded<br />

outer conductive shield connected to<br />

earth, Raychem screened connectors<br />

RSTI are thus suitable for both indoor and<br />

outdoor installations. Oversheath testing<br />

can be performed without removal of the<br />

screened connector<br />

The modern design and material selection<br />

in combination with the Raychem<br />

designed high performance mechanical<br />

lug allows a large application range,<br />

covering most common cable sizes with<br />

just one kit.<br />

The overall and cut back dimensions are<br />

designed for use of minimum space<br />

required in the termination box, even<br />

double connections fit within most<br />

standard boxes.<br />

Raychem screened connectors RSTI are<br />

equipped with a capacitive test point to<br />

determine if the circuit is energised. The<br />

capacitive test point is protected by a<br />

conductive cap.<br />

The screened cable connector<br />

exceeds the requirements of<br />

CENELEC HD 629.1 S1 which includes<br />

BS, VDE and other international<br />

specifications.<br />

Installation<br />

After cable preparation, the lubricated<br />

stress control adapter is simply slid into<br />

place. The high performance multi range<br />

mechanical lugs are quickly installed by<br />

shearing off the bolts. When lubricated,<br />

the screened connector body can easily<br />

be slid onto the cable end and fixed to the<br />

bushing by a threaded pin and nut. The<br />

open end is sealed by a backplug or by a<br />

connection plug, which allows parallel<br />

connection of two cables.<br />

4 2<br />

1<br />

2<br />

3<br />

4<br />

Double connections<br />

For double connections of RSTI-56 series<br />

a T-connector and a coupling connector<br />

(2 T-connectors and a connection plug)<br />

have to be ordered. Installation<br />

dimensions D/d/H of 290 (365)/125 (175)/<br />

285 mm are required.<br />

For double connections of RSTI-76 series<br />

a T-connector and a coupling connector<br />

have to be ordered. Installation dimensions<br />

D/d/H of 325/125/300 mm are<br />

required.<br />

5<br />

Cut-away drawing of<br />

RSTI-56 series T-connector<br />

1Mechanical lug<br />

2 Screened body<br />

3 Stress cone adapter<br />

4 Earthing eye and ground lead<br />

5 Threaded pin<br />

6 Back plug with test point<br />

7 Test point<br />

8 Conductive endcap<br />

D<br />

d<br />

Configuration of RSTI-56 as double<br />

T-connection<br />