Branch joints for screened, 1-core polymeric insulated cables 10 kV, 15 kV and 20 kV<br />

Based on the well proven technology of<br />

medium voltage joints, Raychem offers a<br />

technically and commercially interesting<br />

solution to realise branch joints for single<br />

core polymeric insulated cables. A newly<br />

developed, mechanical connector<br />

integrated in the joint design allows a<br />

quick, simple and reliable installation.<br />

The branch joint is fully qualified to the<br />

Raychem test norm PPS 3013.<br />

<strong>Cable</strong><br />

The branch joint is designed for screened,<br />

single core polymeric insulated cables<br />

10 kV and 20 kV.<br />

For example: NAYSY, NA2XS2Y, ПвП,<br />

АПвП, YHKXS, YHAKXS, XUHAKXS,<br />

AXEKVCY, CXEKVCEY, N(A)2XSY, XHE<br />

49(A), XHP 48(A), EHP 48,<br />

N(A)2XS(F)2Y.<br />

7 8<br />

Design of branch joints<br />

The cables are prepared as for inline<br />

joints. Before connecting the cables, the<br />

screen cut is covered with the yellow<br />

stress grading filler and a stress control<br />

tubing. The three cable ends are<br />

connected with a Raychem designed<br />

mechanical connector with shear-head<br />

bolts. Special moulded parts ensure the<br />

filling and sealing between the branch<br />

cables. Following, similar parts as for<br />

inline joints are used: Yellow void-filler<br />

over the connector, stress control tubing,<br />

dual-wall insulation and screen tubing.<br />

Copper mesh and a mechanical<br />

connector for the screen wires reestablish<br />

the metallic screen. The outer<br />

sealing is provided by a heat-shrinkable,<br />

thick-wall tubing and a 2-finger breakout.<br />

All connectors are supplied with the kit.<br />

Dimensions L, D see table<br />

Branch joint for cables with wire screen, including mechanical connectors<br />

Nominal voltage Cross section Ordering description Dimension (mm)<br />

Uo/U (kV) (mm2 ) L D<br />

35– 95 EPKB 12A/1XU-2XU 550 80<br />

6/10 95–150 EPKB 12B/1XU-2XU 600 90<br />

185–300 EPKB 12C/1XU-2XU 650 95<br />

35– 95 EPKB 24A/1XU-2XU 550 80<br />

8,7/15 95–150 EPKB 24B/1XU-2XU 600 90<br />

185–300 EPKB 24C/1XU-2XU 650 95<br />

35– 95 EPKB 24A/1XU-2XU 550 80<br />

12/20<br />

95–150<br />

120–240<br />

EPKB 24B/1XU-2XU<br />

EPKB 24C/1XU-2XU-BR02<br />

600<br />

650<br />

90<br />

95<br />

185–300 EPKB 24C/1XU-2XU 650 95<br />

Branch joints for other cable types and cross sections are available on request.<br />