Joints for screened, paper insulated cables with one metal sheath per phase<br />

10 kV, 15 kV, 20 kV and 35 kV<br />

<strong>Cable</strong><br />

The joints are designed for single or 3core,<br />

screened, paper insulated (MI,<br />

MIND) cables 10, 15, 20 and 35 kV with<br />

one metal sheath per phase.<br />

For example: ACHPAbI, NAHKBA, AOSB,<br />

OSB-V, AOSB, OSB, AVVB, AVVG,<br />

APVG, ОСБ-В, АОСБ, ОСБ, Hkny,<br />

HAKny, CNKOY, ANKOY, ANKTOYPV,<br />

AMKTOYPV, IPZO 13, NPZO 13,<br />

N(A)EKBA, N(A)KLEY.<br />

7 0<br />

L<br />

D<br />

Design of joints<br />

For three-core cables a solderless earth<br />

connection provides the connection<br />

between the armour and the metal<br />

sheaths. Heat-shrinkable breakouts and<br />

tubing seal and protect the metal sheaths.<br />

A stress grading, oil resistive yellow<br />

mastic is laid around the end of the metal<br />

sheath and the paper cores are<br />

completely covered with oil barrier tubing.<br />

A short conductive tubing rebuilds the<br />

screen from the metal sheath to the<br />

covered paper core.Thus the paper cable<br />

is transformed to a quasi polymeric cable<br />

construction and the cables are jointed<br />

similarly. At the end of the conductive<br />

tubing and over the connectors stress<br />

grading mastic is applied. The jointing<br />

area of each cable core is covered with<br />

a heat-shrinkable stress control tubing.<br />

Aheat-shrinkable dual-wall elastomeric<br />

tubing provides the correct thickness of<br />

insulation and the screening over the<br />

insulation. Copper mesh wrapped around<br />

the joint area rebuilds the metallic screen.<br />

The metal sheaths are jointed with<br />

solderless connections. For three core<br />

cables the armour is replaced by a metal<br />

tape. The outer sealing and protection is<br />

performed by an adhesive coated, thickwall,<br />

heat-shrinkable tubing for single<br />

core cables and by a fibre-reinforced<br />

wraparound for 3-core cables. Joints type<br />

GUSJ are supplied with mechanical<br />

connectors, joints type RPKJ and EPKJ<br />

are supplied without connectors.<br />

3-core paper insulated cable<br />

Dimensions L, D see table