Transition joints for polymeric insulated to paper insulated cables<br />

<strong>Cable</strong><br />

The joints are designed for 4-core paper<br />

and polymeric insulated cables with or<br />

without armour.<br />

For example: N(A)YY, SZAPKOVB,IPO<br />

13, NPO 13, ACHPAbI, AСБУ-AВВГ,<br />

YAKY, YKY, YKYFtly, ANKOY, AYKY, PP<br />

00, PP 41, N(A)YBY, IPO 14, NPO 14,<br />

N(A)KBA.<br />

L<br />

D<br />

Design of joints<br />

The paper cable is transformed to a quasi<br />

polymeric insulated cable with heatshrinkable<br />

oil resistive tubings and a<br />

breakout. The connectors are insulated<br />

and sealed with adhesive coated heat<br />

shrinkable tubing. The outer protection<br />

and sealing is performed by heatshrinkable<br />

tubing.<br />

Dimensions L, D see table<br />

Joints including connectors<br />

The kit includes a solderless earth and<br />

neutral connection system for lead or<br />

aluminium sheaths.<br />

Joints without connerctors<br />

In case of 3-core cables, a separate earth<br />

lead has to be soldered to the metal<br />

sheath (not provided within the kit).<br />

Joints including mechanical connectors for 3- and 4-core paper to 4-core polymeric insulated cable<br />

Nominal voltage Cross section Ordering description for paper cables Dimensions (mm)<br />

Uo/U (kV) (mm2 ) 3-core 4-core L D<br />

10– 35 – TRAJ-01/4x 10- 35/4SB 500 50<br />

0,6/1<br />

25– 70<br />

70–120<br />

TRAJ-01/4x 25- 70/3SB<br />

TRAJ-01/4x 70-120/3SB<br />

TRAJ-01/4x 25- 70/4SB<br />

TRAJ-01/4x 70-120/4SB<br />

800<br />

900<br />

70<br />

80<br />

150–240 TRAJ-01/4x150-240/3SB TRAJ-01/4x150-240/4SB 1100 110<br />

Joints without connectors<br />

4-core paper to 4-core unarmoured polymeric insulated cable including solderless earth connection for use with mechanical<br />

connectors<br />

Nominal voltage Cross section Ordering description Dimensions (mm)<br />

polymeric paper Max. connector Joint<br />

Uo/U (kV) (mm2 ) Length Diameter L D<br />

25– 95 25– 95 SMOE 81404 90 25 850 70<br />

0,6/1 95–150 50–150 SMOE 81502 130 32 1050 80<br />

95–240 95–240 SMOE 81400 110 38 1150 90<br />

Note: Dimensions of connectors must not exceed the dimensions given in the table. Mechanical connectors are not included in the joints.<br />

4-core paper to 4-core polymeric insulated cable for use with crimp connectors<br />

Nominal voltage Cross section Ordering description for plastic cables Dimensions (mm)<br />

Uo/U (kV) (mm2 ) without armour with armour L D<br />

10– 16 EPKJ 0903 EPKJ 0828 700 45<br />

0,6/1<br />

25– 50<br />

70–150<br />

EPKJ 0910<br />

EPKJ 0917<br />

EPKJ 0835<br />

EPKJ 0842<br />

900<br />

1100<br />

60<br />

75<br />

185–300 EPKJ 0924 EPKJ 0856 1300 100<br />

5 1