Wall feed-through EPAF<br />

Application<br />

The wall feed-through EPAF provides a<br />

reliable seal against water and gas for<br />

cables brought into buildings<br />

underground. When properly installed,<br />

test reports prove a water and gas<br />

tightness at an external pressure of 0,1<br />

MPa between the wall and the feedthrough<br />

as well as between the feedthrough<br />

and the cables. The design<br />

allows removal of cables and installation<br />

of new cables in the same feed-through.<br />

For exceptionally thick walls, the feedthrough<br />

can be easily prolonged with<br />

another one.<br />

8 6<br />

H<br />

Construction<br />

The feed-through EPAF consists of a<br />

galvanised steel spiral over which a<br />

longer heat-shrinkable tubing with an<br />

adhesive coating inside is installed. An<br />

external coating of special primer<br />

improves the adhesion to various types of<br />

concrete and quick-drying cements. The<br />

ends of the tubing are protected with caps<br />

to allow cable installations at a later<br />

stage. When installing the cable, the end<br />

caps are removed and the adhesive<br />

coated tubing shrinks onto the cable.<br />

<strong>Cable</strong>s are removed by cutting off the<br />

tubing at the end of the steel spiral. Upon<br />

pulling the steel spiral with a pair of pliers,<br />

it will break at a predetermined breaking<br />

point. The resulting new open end of the<br />

heat-shrinkable tubing can be shrunk onto<br />

the new cable.<br />

1 Sealing cap<br />

2 Outside sealing coating<br />

3 Inside sealing coating<br />

4 Heat-shrinkable tubing<br />

5 Predetermined breaking point<br />

6 Galvanised steel spiral<br />

Da: Inside diameter as delivered<br />

Db: Diameter after free recovery<br />

L: Length<br />

W: Wall thickness<br />

Recommended application ranges (mm) Ordering Dimensions (mm)<br />

<strong>Cable</strong> diameter Wallthickness Hole diameter description D L R<br />

min. max. W max.* H min. a (min.) b (max.) ± 20 mm ± 20 mm<br />

8 14 320 40 EPAF 2004 16 8 700 90<br />

12 25 320 55 EPAF 2008 28 10 700 90<br />

18 36 420 70 EPAF 2010 41 16 800 90<br />

29 56 320 90 EPAF 2020 59 26 700 90<br />

55 98 370 140 EPAF 2030 106 54 760 115<br />

* For bigger walls two wall feed-through can easily be connected.<br />