6.14 OPERATION WITH LOW TEMPERATURE CHILLED WATER AT EVAPORATOR<br />

With temperatures lower than 6 °C, the hydraulic circuit should be filled with a suitable water and antifreeze<br />

solution. In such cases the service thermostat and the freeze protection thermostat must be reset:<br />

These calibrations are normally factory set.<br />

Units from the normal production range are not designed to operate<br />

with chilled water temperatures lower than 6 °C, at the evaporator<br />

outlet. To operate outside this limit the unit may require structural<br />

modifications. If this is necessary contact Bluebox.<br />

The ethylene glycol percentage must be selected in relation to the required chilled water temperature.<br />

See table 1.<br />

TABLE 1 - FREEZING POINT FOR WATER-ANTIFREEZE MIXTURES<br />

LIQUID OUTLET TEMPERATURE<br />

OR MINIMUM AMBIENT TEMPERATURE (°C)<br />

FREEZING POINT (°C) -5° -10° -15° -20° -25° -30° -35° -40° -45°<br />

ANTIFREEZE<br />

ETHYLENE GLYCOL 6 22 30 36 41 46 50 53 56<br />

PROPYLENE GLYCOL 15 25 33 39 44 48 51 54 57<br />

METHANOL 8 14 20 26 30 34 38 41 45<br />

CALCIUM CHLORIDE 9 14 18 21 24 26 27 28 30<br />

TEMPER -20<br />

T -20°C<br />

---<br />

TEMPER -40 T -40°C<br />

---<br />

TEMPER -60<br />

+0° -5° -10° -15° -20° -25°<br />

-30° -35° -40°<br />

TIFOXITE 40<br />

50 60 63 69 73 ---<br />

FREEZIUM 10 20 25 30 34 37 40 43 45<br />

PEKASOL 50 50 59 68 75 81 86 90 ---<br />

If ambient temperatures lower than the freezing point of water can<br />

be expected, antifreeze mixtures in the above indicated percentage<br />

must be utilized.<br />

In the case of ST versions with a glycol content greater than 30% pumps<br />

with special seals must be specified at the time of the order.<br />

Blue Box 33<br />

% BY WEIGHT<br />

T -60°C