<strong>KAPPA</strong> V <strong>ECHOS</strong> /DS: unit with desuperheater<br />
In addition to the components of version <strong>KAPPA</strong> V <strong>ECHOS</strong> this unit includes a heat recovery brazed plate type<br />
condenser for condensation partial heat recovery (20%) arranged in series for each circuit with the condenser<br />
coil. For the maximum efficiency of the device it is advisable to couple with fan speed control. Also available on<br />
all HP models. In this case an isolating valve must be fitted on the water recovery circuit and be closed during heat<br />
pump mode operation as described in the manual.<br />
<strong>KAPPA</strong> V <strong>ECHOS</strong> /LN: low noise unit<br />
In addition to the components of version <strong>KAPPA</strong> V <strong>ECHOS</strong> this unit includes:<br />
An internally lined sound absorbing compressor compartment, with absorption material having an intermediate<br />
layer of high acoustic impedance material, and fan speed control. The fan speed is automatically increased in<br />
accordance with the ambient conditions.<br />
<strong>KAPPA</strong> V <strong>ECHOS</strong> /SLN: extra low noise unit<br />
In addition to the components of version <strong>KAPPA</strong> V <strong>ECHOS</strong>/LN this unit includes:<br />
An increased coil surface area, slower fan speed 8 pole motors and fan speed control.<br />
REFRIGERANT CIRCUIT <strong>AC</strong>CESSORIES<br />
- Electronic expansion valve<br />
- Condensing pressure control by fan speed regulator for low ambient temperature operation<br />
- Dual set-point (high/low temperature) with unique electronic thermostatic valve. The evaporator of the unit is<br />
sized according to the higher operating temperature. The two set-points can be programmed and switched<br />
between them from the keypad or using a digital input; the type of selection must be specified at the time of the<br />
order.<br />
- High and low pressure gauges are available ,as an option, for all models. As standard on all units low pressure<br />
values and relative, condensation and evaporation temperatures are measured by pressure transducers that<br />
relay signals that are displayed on the controller.<br />
- Liquid receiver (standard for version /HP, /DC);<br />
- Compressor suction valves;<br />
- Liquid line solenoid valve. The units have as standard a device which,at the compressor stop, closes the liquid<br />
line and consequently the expansion valve;<br />
- low water temperature kit.<br />
HYDRAULIC CIRCUIT <strong>AC</strong>CESSORIES<br />
- Anti-freeze evaporator heater, also on recovery heat exchangers if available. ST version also has an anti-freeze<br />
heater on the hydraulic circuit and storage tank<br />
- Water side relief valve (version ST only).<br />
ELECTRICAL <strong>AC</strong>CESSORIES<br />
- Serial interface RS485 type with Carel, Modbus, Echelon and Bacnet protocols. Compatibility with Trend and<br />
Johnson supervisions.<br />
- Power factor correction cos f ≥ 0.9 at nominal operating conditions; on external IP 55 electric panel on<br />
external IP 55 electric panel (connections to power supply are the responsibility of the installer; accessory<br />
connected to potential free contacts)<br />
- Remote user terminal panel (in addition to the standard terminal)<br />
- Set point variable with remote signal (0-1V, 0-10V, 0-20mA, 4-20mA)<br />
- Single voltage-free contacts for machine status signals<br />
- 3 levels of alarm priority<br />
- SMS availability for assistance management<br />
- Limitation of absorbed current<br />