<strong>KAPPA</strong> V <strong>ECHOS</strong> /DS: unit with desuperheater<br />

In addition to the components of version <strong>KAPPA</strong> V <strong>ECHOS</strong> this unit includes a heat recovery brazed plate type<br />

condenser for condensation partial heat recovery (20%) arranged in series for each circuit with the condenser<br />

coil. For the maximum efficiency of the device it is advisable to couple with fan speed control. Also available on<br />

all HP models. In this case an isolating valve must be fitted on the water recovery circuit and be closed during heat<br />

pump mode operation as described in the manual.<br />

<strong>KAPPA</strong> V <strong>ECHOS</strong> /LN: low noise unit<br />

In addition to the components of version <strong>KAPPA</strong> V <strong>ECHOS</strong> this unit includes:<br />

An internally lined sound absorbing compressor compartment, with absorption material having an intermediate<br />

layer of high acoustic impedance material, and fan speed control. The fan speed is automatically increased in<br />

accordance with the ambient conditions.<br />

<strong>KAPPA</strong> V <strong>ECHOS</strong> /SLN: extra low noise unit<br />

In addition to the components of version <strong>KAPPA</strong> V <strong>ECHOS</strong>/LN this unit includes:<br />

An increased coil surface area, slower fan speed 8 pole motors and fan speed control.<br />

REFRIGERANT CIRCUIT <strong>AC</strong>CESSORIES<br />

- Electronic expansion valve<br />

- Condensing pressure control by fan speed regulator for low ambient temperature operation<br />

- Dual set-point (high/low temperature) with unique electronic thermostatic valve. The evaporator of the unit is<br />

sized according to the higher operating temperature. The two set-points can be programmed and switched<br />

between them from the keypad or using a digital input; the type of selection must be specified at the time of the<br />

order.<br />

- High and low pressure gauges are available ,as an option, for all models. As standard on all units low pressure<br />

values and relative, condensation and evaporation temperatures are measured by pressure transducers that<br />

relay signals that are displayed on the controller.<br />

- Liquid receiver (standard for version /HP, /DC);<br />

- Compressor suction valves;<br />

- Liquid line solenoid valve. The units have as standard a device which,at the compressor stop, closes the liquid<br />

line and consequently the expansion valve;<br />

- low water temperature kit.<br />

HYDRAULIC CIRCUIT <strong>AC</strong>CESSORIES<br />

- Anti-freeze evaporator heater, also on recovery heat exchangers if available. ST version also has an anti-freeze<br />

heater on the hydraulic circuit and storage tank<br />

- Water side relief valve (version ST only).<br />

ELECTRICAL <strong>AC</strong>CESSORIES<br />

- Serial interface RS485 type with Carel, Modbus, Echelon and Bacnet protocols. Compatibility with Trend and<br />

Johnson supervisions.<br />

- Power factor correction cos f ≥ 0.9 at nominal operating conditions; on external IP 55 electric panel on<br />

external IP 55 electric panel (connections to power supply are the responsibility of the installer; accessory<br />

connected to potential free contacts)<br />

- Remote user terminal panel (in addition to the standard terminal)<br />

- Set point variable with remote signal (0-1V, 0-10V, 0-20mA, 4-20mA)<br />

- Single voltage-free contacts for machine status signals<br />

- 3 levels of alarm priority<br />

- SMS availability for assistance management<br />

- Limitation of absorbed current<br />