SYMPTOM<br />

E)<br />

No compressor<br />

running. Display On:<br />

OPERATION<br />

COOLING HEATING<br />

PROBABLE CAUSE<br />

˜ ˜ 220V fuses burnt-out<br />

(FU51)<br />

unit ON with alarm<br />

“High Pressure<br />

Compressor 1, 2” ˜ Fans contactor not<br />

energised<br />

F)<br />

No compressor<br />

running. Display On:<br />

unit ON with alarm<br />

“Fans protection”<br />

G)<br />

No compressor<br />

running. Display On:<br />

unit ON with alarm<br />

“Thermal protections<br />

Compressor 1, 2”<br />

Blue Box 54<br />

POSSIBLE CORRECTIVE <strong>AC</strong>TION<br />

Change fuses. If fuses burn-out<br />

again, contact assistance<br />

Check voltage across the<br />

contactor coil and coil continuity<br />

˜ Fan fuses burnt-out (FU21) Check cause of burn-out and<br />

change fuses.<br />

˜ Fan motor faulty Check and replace if necessary<br />

˜ ˜ Fan thermal protection<br />

intervention<br />

Check insulation between<br />

windings and from windings to<br />

earth (ground)<br />

˜ ˜ Fan motor faulty Check and replace if necessary<br />

˜ ˜ Faulty fan alarm relay Check and replace relay<br />

˜ ˜ Drop in power feeding<br />

voltage<br />

˜ ˜ Setting of thermal<br />

protections<br />

Check voltage stability and fit<br />

appropriate protection if<br />

necessary<br />

Contact assistance<br />

˜ ˜ Circuits partially discharged Call service to replenish charge