7.2.13 Low ambient temperature kit (option - condensing control with fan speed<br />
regulator)<br />
As the ambient air temperature decreases the necessary condensing pressure for correct operation of the chiller<br />
cycle is maintained, within the machine operating range, by adjusting the cooling air-flow through the condenser.<br />
Condensing pressure control is only active when the machine is operating in chiller mode.<br />
When the unit is operating in heat pump mode this function is inhibited and the fans are forced to their maximum<br />
speed.<br />
The controller checks the condensing pressure and adjusts fan speed on the basis of the circuit with the highest<br />
pressure reading. The speed regulator adjusts fan speed with a phase control system that minimises problems<br />
related to electromagnetic compatibility.<br />
Speed control is available over a 20-100% range. At the time of start-up the fans always run at 40% nominal<br />
speed.<br />
7.2.14 Changeover from chiller to heat pump and vice versa<br />
The changeover from chiller to heat pump and back can be performed at any time, either by means of an<br />
external signal on a digital input, from the keypad, or via the serial line. The operating mode changeover must be<br />
only seasonal and only with the unit off.<br />
After a mode changeover, the controller re-starts the unit in the new mode with a factory set minimum delay<br />
time.<br />