SYMPTOM<br />

OPERATION<br />

COOLING HEATING<br />

PROBABLE CAUSE<br />

Blue Box 59<br />

POSSIBLE CORRECTIVE <strong>AC</strong>TION<br />

U)<br />

One or more ˜ ˜ Unit capacity step active Normal operation<br />

compressors Off.<br />

Display On<br />

without alarms ˜ ˜ Fuses burnt-out Call service organisation<br />

V)<br />

All compressors<br />

running. Display On<br />

with alarm<br />

“Compressor<br />

Maintenance”<br />

W)<br />

All compressors<br />

running. Display On<br />

with alarm “Unit<br />

Maintenance”<br />

˜ ˜ Faulty controller Call service organisation<br />

˜ ˜ No external consent to<br />

compressor<br />

˜ ˜ Compressors specified by<br />

alarm require maintenance<br />

Check compressor external<br />

consent<br />

Call service for scheduled<br />

maintenance<br />

˜ ˜ Unit maintenance required Call service for scheduled<br />

maintenance<br />

X)<br />

All compressors<br />

running without<br />

stopping. Display<br />

˜ ˜ Excessive thermal load Call service organisation<br />

On without alarm ˜ ˜ Refrigerant circuits partially<br />

discharged<br />

Call service organisation<br />

˜ Liquid refrigerant filter<br />

clogged<br />

Clean or replace<br />

˜ ˜ Controller not working Call service organisation<br />

˜ 4-way reversing valve not<br />

energised<br />

Check power supply and<br />

solenoid valve coils and replace if<br />

necessary