SYMPTOM<br />
OPERATION<br />
COOLING HEATING<br />
PROBABLE CAUSE<br />
Blue Box 59<br />
POSSIBLE CORRECTIVE <strong>AC</strong>TION<br />
U)<br />
One or more ˜ ˜ Unit capacity step active Normal operation<br />
compressors Off.<br />
Display On<br />
without alarms ˜ ˜ Fuses burnt-out Call service organisation<br />
V)<br />
All compressors<br />
running. Display On<br />
with alarm<br />
“Compressor<br />
Maintenance”<br />
W)<br />
All compressors<br />
running. Display On<br />
with alarm “Unit<br />
Maintenance”<br />
˜ ˜ Faulty controller Call service organisation<br />
˜ ˜ No external consent to<br />
compressor<br />
˜ ˜ Compressors specified by<br />
alarm require maintenance<br />
Check compressor external<br />
consent<br />
Call service for scheduled<br />
maintenance<br />
˜ ˜ Unit maintenance required Call service for scheduled<br />
maintenance<br />
X)<br />
All compressors<br />
running without<br />
stopping. Display<br />
˜ ˜ Excessive thermal load Call service organisation<br />
On without alarm ˜ ˜ Refrigerant circuits partially<br />
discharged<br />
Call service organisation<br />
˜ Liquid refrigerant filter<br />
clogged<br />
Clean or replace<br />
˜ ˜ Controller not working Call service organisation<br />
˜ 4-way reversing valve not<br />
energised<br />
Check power supply and<br />
solenoid valve coils and replace if<br />
necessary