10.3.3 Refrigerant charge<br />

- Connect the refrigerant gas cylinder to the male 1/4 SAE charge connector on the liquid line and allow a small<br />

amount of gas to escape in order to purge the connection hose of air.<br />

- The circuit must be charged exclusively with liquid; therefore, if the cylinder is not equipped with a dip pipe it<br />

must be turned upside-down.<br />

10.4 ENVIRONMENTAL CONSIDERATIONS<br />

Units operating with R407C must be charged exclusively with liquid<br />

refrigerant by way of the charge connection on the liquid line.<br />

A unit that was originally factory charged with R407C cannot be<br />

charged with R22 (and vice versa)!<br />

Laws governing the use of substances detrimental to the ozone layer prohibit the dispersal of refrigerant gases in<br />

the environment, obliging users to recover refrigerants at the end of their useful life and consign them to the<br />

dealer or to specific collection centres.<br />

Refrigerant R407C IS mentioned among substances subject to special monitoring regimes established by law, and<br />

as such they are subject to the prescriptions indicated above.<br />

11. TROUBLESHOOTING<br />

Use special care during maintenance work in order to limit the risk of<br />

refrigerant leakage as far as possible.<br />

The following pages contain a list of the most common causes that can result in the shutdown or anomalous<br />

operation of the chiller. Faults are arranged in accordance with easily identifiable symptoms.<br />

In relation to possible corrective action, adopt the maximum attention<br />

in the operations you intend to perform as overconfidence coupled<br />

with insufficient attention due to lack of expertise can lead to serious<br />

accidents. We therefore recommend that Blue Box or other skilled<br />

HV<strong>AC</strong> engineers are contacted to identify and correct the problem.<br />

Blue Box 52