SYMPTOM<br />
H)<br />
No compressor<br />
running. Display On:<br />
OPERATION<br />
COOLING HEATING<br />
PROBABLE CAUSE<br />
˜ Insufficient percentage of<br />
glycol in hydraulic circuit<br />
unit ON with alarm<br />
“Low Pressure<br />
compressor 1, 2” ˜ ˜ Both circuits have<br />
insufficient refrigerant<br />
charge<br />
I)<br />
No compressor<br />
running. Display On:<br />
unit ON with alarm<br />
˜ Fans contactor not<br />
energised<br />
Blue Box 55<br />
POSSIBLE CORRECTIVE <strong>AC</strong>TION<br />
Restore correct glycol percentage<br />
Find possible leaks in circuit,<br />
repair, and recharge<br />
Check voltage across the<br />
contactor coil and coil continuity<br />
˜ Fan motor faulty Check and replace if necessary<br />
˜ Insufficient water flow to<br />
evaporator<br />
˜ Incorrect setting of defrost<br />
set-point<br />
˜ Insufficient water flow to<br />
evaporator<br />
Check hydraulic circuit<br />
Check and correct setting if<br />
necessary<br />
Increase water flow to<br />
evaporator and check<br />
temperature rise<br />
“Exceeded Threshold<br />
Low Temperature of<br />
leaving User Water” ˜ ˜ Faulty controller Contact service organisation<br />
J)<br />
No compressor<br />
running. Display On:<br />
unit ON with alarm<br />
“Exceeded Threshold<br />
Low Temperature User<br />
Water Reference”<br />
˜ Defrost sensor short circuit Contact service organisation<br />
˜ Excessive thermal load Reduce thermal load