SYMPTOM<br />

H)<br />

No compressor<br />

running. Display On:<br />

OPERATION<br />

COOLING HEATING<br />

PROBABLE CAUSE<br />

˜ Insufficient percentage of<br />

glycol in hydraulic circuit<br />

unit ON with alarm<br />

“Low Pressure<br />

compressor 1, 2” ˜ ˜ Both circuits have<br />

insufficient refrigerant<br />

charge<br />

I)<br />

No compressor<br />

running. Display On:<br />

unit ON with alarm<br />

˜ Fans contactor not<br />

energised<br />

Blue Box 55<br />

POSSIBLE CORRECTIVE <strong>AC</strong>TION<br />

Restore correct glycol percentage<br />

Find possible leaks in circuit,<br />

repair, and recharge<br />

Check voltage across the<br />

contactor coil and coil continuity<br />

˜ Fan motor faulty Check and replace if necessary<br />

˜ Insufficient water flow to<br />

evaporator<br />

˜ Incorrect setting of defrost<br />

set-point<br />

˜ Insufficient water flow to<br />

evaporator<br />

Check hydraulic circuit<br />

Check and correct setting if<br />

necessary<br />

Increase water flow to<br />

evaporator and check<br />

temperature rise<br />

“Exceeded Threshold<br />

Low Temperature of<br />

leaving User Water” ˜ ˜ Faulty controller Contact service organisation<br />

J)<br />

No compressor<br />

running. Display On:<br />

unit ON with alarm<br />

“Exceeded Threshold<br />

Low Temperature User<br />

Water Reference”<br />

˜ Defrost sensor short circuit Contact service organisation<br />

˜ Excessive thermal load Reduce thermal load