CHAPTER 5: ADVANCED MODBUS PROGRAMMING<br />
Determining Modbus Unit ID <strong>and</strong> Register Address<br />
To read <strong>and</strong> write, you need to determine the Modbus Unit ID <strong>and</strong> Register Address that are<br />
equivalent to the brain’s memory map address. You can use ioManager to convert addresses. The<br />
basic steps are shown below; see the ioManager User’s Guide for additional help. You may also<br />
need Appendix A to find memory map addresses.<br />
1. In the ioManager main window, with a configuration file open, right-click an I/O unit <strong>and</strong><br />
choose Configure from the pop-up menu.<br />
2. In the Configure I/O Units dialog box, click the Others button <strong>and</strong> choose Modbus from the<br />
pop-up menu.<br />
3. Click the Advanced button to see the rest of the dialog box.<br />
100 SNAP Ethernet-Based I/O Units Protocols <strong>and</strong> Programming Guide