APPENDIX A: SNAP ETHERNET-BASED BRAIN MEMORY MAP<br />
Starting Address Length Type Description<br />
FFFF F030 0048 4 UI Brain sends BootP request when turned on.<br />
0 (default) = Only if brain’s IP address is 0.0.0.0.<br />
1 = Whenever brain is turned on.<br />
FFFF F030 004C 4 B Degrees are in F or C (Boolean)<br />
0 = degrees C; non-0 = degrees F<br />
FFFF F030 0050 4 -- Reserved<br />
FFFF F030 0054 4 UI Watchdog time in milliseconds (unsigned integer).<br />
0 means watchdog is disabled.<br />
FFFF F030 0058 4 UI TCP/IP minimum Response Timeout (RTO) in milliseconds. TCP/IP<br />
calculates the RTO <strong>based</strong> on past network response times. The<br />
default is a minimum 3000 msec between retries.<br />
FFFF F030 005C 4 UI Digital scan counter. Counts the number of digital scans; can be<br />
used for benchmarking.<br />
FFFF F030 0060 4 UI Analog scan counter. Counts the number of analog scans; can be<br />
used for benchmarking.<br />
FFFF F030 0064 4 UI Initial RTO<br />
FFFF F030 0068 4 UI TCP number of retries<br />
FFFF F030 006C 4 UI TCP idle session timeout<br />
FFFF F030 0070 4 UI Ethernet errors: late collisions. This <strong>and</strong> the next two sets of<br />
addresses indicate problems on your Ethernet network, often due to<br />
length of the segment or number of devices. Late collisions are not<br />
normal. Normally two Ethernet hosts trying to talk at once collide<br />
early in the packet <strong>and</strong> both back off, or the second host waits.<br />
FFFF F030 0074 4 UI Ethernet errors: excessive collisions. Indicate that all the backup<br />
attempts to communicate have been exhausted.<br />
FFFF F030 0078 4 UI Ethernet errors: other<br />
FFFF F030 007C 4 M “Smart” modules present. Bitmask showing the presence of analog<br />
<strong>and</strong> serial modules. Present = 1; not present = 0. Use as a<br />
troubleshooting tool to make sure modules are online.<br />
FFFF F030 0080 20 S-ZT Brain’s part number (string)<br />
Last valid address for this area: FFFF F030 009F<br />
106 SNAP Ethernet-Based I/O Units Protocols <strong>and</strong> Programming Guide