APPENDIX A: SNAP ETHERNET-BASED BRAIN MEMORY MAP<br />

Starting Address Length Type Description<br />

FFFF F110 00E0 4 UI Alarm 1: Address of value to check. Use to set multiple alarms on<br />

one point. See brain user’s <strong>guide</strong> for information.<br />

FFFF F110 00E4 4 UI Alarm 1: Is value a float? Yes = 1; no = 0. Yes is default.<br />

FFFF F110 00E8 18 -- Pad for alignment<br />

(Additional alarms follow in order on even 80 hex boundaries.)<br />

FFFF F110 1F80 80 -- Alarm 63<br />

Last valid address for this area: FFFF F110 1FFF<br />

Event Message Configuration—Read/Write<br />

(Does not apply to SNAP Simple I/O) See page 34 in this <strong>guide</strong> <strong>and</strong> the ioManager User’s Guide<br />

for information on configuring messages as reactions to events or alarms. Only the first two<br />

messages are shown. Other messages follow the same pattern.<br />

Starting Address Length Type Description<br />

FFFF F120 0000 4 UI Message 0: Current message state. Messages become active when<br />

Scratch Pad conditions are met. To acknowledge receipt of an active<br />

message, write a 2 to this address. The message will not be sent<br />

again until the conditions are met again.<br />

0 = Inactive, 1 = Active, 2 = Acknowledged<br />

FFFF F120 0004 8 M Message 0: Scratch Pad bits on? (mask)<br />

FFFF F120 000C 8 M Message 0: Scratch Pad bits off? (mask)<br />

FFFF F120 0014 4 B Message 0: Enable streaming (Boolean). Be sure to fill in streaming<br />

configuration section. (See page 118.)<br />

FFFF F120 0018 4 UI Message 0: Stream period in seconds<br />

0 = send once, 604800 = maximum<br />

FFFF F120 001C 4 B Message 0: Enable email (Boolean). Be sure to fill in email<br />

configuration section. (See page 138.)<br />

FFFF F120 0020 4 UI Message 0: Email period in seconds<br />

0 = send once; 604800 = maximum<br />

FFFF F120 0024 4 B Message 0: Enable SNMP trap (Boolean).<br />

0 = disable; non-0 = enable<br />

FFFF F120 0028 4 UI Message 0: SNMP trap period in seconds<br />

0 = send once; 604800 = maximum<br />

FFFF F120 002C 4 UI Message 0: SNMP trap type<br />

FFFF F120 0030 4 UI Message 0: Priority. 0 = high; 1 = low. High is default. Applies only if<br />

you are using SNMP with a modem connection, <strong>and</strong> the brain is<br />

dialing out.<br />

FFFF F120 0034 4 -- Reserved<br />

136 SNAP Ethernet-Based I/O Units Protocols <strong>and</strong> Programming Guide