APPENDIX A: SNAP ETHERNET-BASED BRAIN MEMORY MAP<br />
Analog Point Write—Read/Write<br />
Although this area is read/write, you would normally write to it. See “IEEE Float Data” on<br />
page 43 for help in formatting data.<br />
Only the first three points are shown in the table. Each successive point starts on an even 40 hex<br />
boundary <strong>and</strong> follows the same pattern.<br />
Starting Address Length Type Description<br />
FFFF F0B0 0000 4 F Point 0: Output analog data (float—Engineering Units)<br />
FFFF F0B0 0004 4 F Point 0: Output analog data (float—counts)<br />
FFFF F0B0 000C 4 F Point 0: TPO period (float—<strong>units</strong> of time in seconds. Valid range:<br />
0.25 to 64.0 seconds, in 0.25 steps.)<br />
FFFF F0B0 0040 4 F Point 1: Output analog data (float—Engineering Units)<br />
FFFF F0B0 0044 4 F Point 1: Output analog data (float—counts)<br />
FFFF F0B0 004C 4 F Point 1: TPO period (float—<strong>units</strong> of time in seconds. Valid range:<br />
0.25 to 64.0 seconds, in 0.25 steps.)<br />
FFFF F0B0 0080 4 F Point 2: Output analog data (float—Engineering Units)<br />
FFFF F0B0 0084 4 F Point 2: Output analog data (float—counts)<br />
FFFF F0B0 008C 4 F Point 2: TPO period (float—<strong>units</strong> of time in seconds. Valid range:<br />
0.25 to 64.0 seconds, in 0.25 steps.)<br />
(Additional points follow in order on even 40 hex boundaries.)<br />
FFFF F0B0 0FC0 4 F Point 63: Output analog data (float—Engineering Units)<br />
Last valid address for this area: FFFF F0B0 0FCF<br />
124 SNAP Ethernet-Based I/O Units Protocols <strong>and</strong> Programming Guide