An SDO is structured as follows:<br />

Identifier Command<br />

code<br />

Example:<br />

600 h+<br />

Node-ID<br />

Index<br />

(low) (high)<br />

<strong>CAN</strong>open-Software<br />

Sub-index LSB Data field MSB<br />

23 h 00 14 h 01 7F h 04 h 00 00<br />

(write)<br />

Description of the SDOs:<br />

(Index=1400 h)<br />

(Receive-PDO-Comm-Para)<br />

(COB-def.) COB = 047F h<br />

Identifier ....... The parameters are transmitted on ID ‘600 h + NodeID’ (request).<br />

The receiver acknowledges the parameters on ID ‘580 h + NodeID’ (response).<br />

Command code . . The command code transmitted consists among other things of the command<br />

specifier and the length. Frequently required combinations are, for instance:<br />

40 h = 64 dec : Read Request, i.e. a parameter is to be read<br />

23 h = 35 dec : Write Request with 32-bit data, i.e. a parameter is to be set<br />

The <strong>CAN</strong>-<strong>CBX</strong>-<strong>AI420</strong> module responds to every received telegram with a<br />

response telegram. This can contain the following command codes:<br />

43 h = 67 dec : Read Response with 32 bit data, this telegram contains the<br />

parameter requested<br />

60 h = 96 dec : Write Response, i.e. a parameter has been set successfully<br />

80 h = 128 dec : Error Response, i.e. the <strong>CAN</strong> module reports a communication error<br />

<strong>CAN</strong>-<strong>CBX</strong>-<strong>AI420</strong> Manual Rev. 1.3 33