preventing epoxy coating, and from the outside with bitumastic/coal tar based<br />

waterpro<strong>of</strong> coating.<br />

Cleanouts shall be installed in concrete pad flush with surface for HS 20 rated<br />

installation.<br />

SW 5.3 EXTERIOR DOMESTIC WATER AND CHILLED WATER PIPING<br />

Piping mains shall be a minimum <strong>of</strong> 6" in diameter. Domestic water piping shall have a<br />

minimum <strong>of</strong> 3'-0" ground cover. Chilled water piping shall have a minimum <strong>of</strong> 4’-0”<br />

ground cover. All buried water lines shall have a sand or stone dust bed and cover.<br />

Valves shall be installed at all piping branch-<strong>of</strong>fs.<br />

Underground water distribution pipe shall be asphalt coated, cement lined ductile iron,<br />

Class 52 or higher, with flexible restrained joints. All fittings and hardware shall be epoxy<br />

coated.<br />

The buried chilled water supply pipe shall be insulated. Field installed rigid foam glass<br />

with 50 mil poly jacket is preferred; however, pre-insulated double wall pipe is<br />

acceptable.<br />

New chilled and domestic water branches shall preferably be connected to existing<br />

mains with full size tees; reducing tees or wet taps can be only be used with prior<br />

approval <strong>of</strong> UVa Energy and Utilities Department. Resilient seat gate valves shall be<br />

provided at the connection point to the main; where full size tees are used the valve<br />

shall be full size and upstream <strong>of</strong> any reducer.<br />

The entry point into buildings shall be with factory flanged ductile iron, Class 53 or<br />

higher.<br />

Branch lines 2 ½” and smaller shall be copper type "K".<br />

Water lines shall be tested to 200 psig.<br />

Domestic water lines shall be bacteria tested.<br />

SW 4 SITE DRAINAGE SYSTEMS 110