Provide thermometers (or temperature gauges) on all four legs <strong>of</strong> water-to-water heat<br />

exchangers, and on both fluid legs <strong>of</strong> steam converters.<br />

All fired or unfired pressure vessels whether a part <strong>of</strong> an equipment package or an<br />

entire piece <strong>of</strong> equipment shall be specified to comply with the ASME Code. The<br />

specifications shall require that the pressure vessel be so stamped in an easily<br />

identifiable location and that the manufacturer’s data indicating ASME compliance be<br />

submitted.<br />

Comply with the Boiler and Pressure Vessel Rules and Regulations issued by DLI.<br />

BSRV 4.3.3.4 EXPANSION JOINTS<br />

Expansion joints on heating pipe shall be class 300 packed slip type or ball joints,<br />

packable under pressure. Bellows type expansion joints shall not be used. Expansion<br />

joints on HPS, pumped condensate and MTHW shall have welded joints rather than<br />

flanges. Where appropriate slip expansion joints with an integral foot can be used in lieu<br />

<strong>of</strong> an expansion joint and separate anchor. Acceptable manufacturers are Adsco,<br />

Advanced Thermal Systems, and Yarway. Provide calcium silicate insulation on the main<br />

body <strong>of</strong> the expansion joints and provide a removable flexible insulation blanket that<br />

over laps the calcium silicate by 4” on each side. Install slip expansion joints so the pipe<br />

expands into the joint in the direction <strong>of</strong> flow.<br />

BSRV 4.3.3.5 INSULATION<br />

Insulation in steam and MTHW tunnels shall be fiberglass rated for 800 degrees F with<br />

an aluminum jacket or calcium silicate with waterpro<strong>of</strong> 30 pound felt jacketing; applied<br />

to fittings with waterpro<strong>of</strong> adhesive and copper or stainless steel wires. Insulation on<br />

high pressure steam, pumped condensate, and MTHW in mechanical rooms shall be<br />

fiberglass rated for 800 degrees or calcium silicate with a glued canvas jacket. The<br />

minimum insulation thickness on HPS and MTHW shall be 4” on pipe 6” and above and<br />

3” on pipe 4” and smaller. Removable insulation blankets with double D-rings and<br />

straps shall be provided on all steam, condensate and hot water valves and fittings that<br />

cannot be properly fitted with fiberglass or calcium silicate insulation.<br />

BSRV 4.3.3.6 MISC HEATING COMPONENTS<br />

All duct reheat coils shall have access doors or panels to allow door inspection and<br />

cleaning <strong>of</strong> coil inlet.<br />

Adequate room shall be provided to remove hot water coils for cleaning and/or repair.<br />

All fittings on secondary hot water systems shall be class 150 or better.<br />

Paper/compressed fiber flange gaskets shall not be used.<br />

BSRV 4 HEATING, VENTILATION, AND AIR CONDITIONING 191