Facility Design Guidelines - Facilities Management - University of ...
Facility Design Guidelines - Facilities Management - University of ...
Facility Design Guidelines - Facilities Management - University of ...
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
ecirculating systems shall have a means to pre-cool and dehumidify outside<br />
air before being mixed with the return air rather than cooling the entire<br />
supply airstream to dehumidify and then reheating. A chilled water coil,<br />
heat recovery device or other method approved by <strong>Facilities</strong> <strong>Management</strong><br />
may be used.<br />
o) Sequence will specify if fans run continuously or can be shut <strong>of</strong>f. Supply,<br />
return, and exhaust fans shall be interlocked as required.<br />
p) AHUs should have manual override to run unit with high outside airflow (for<br />
venting odors from new carpet/furniture, floods, etc.)<br />
q) In buildings that do not have other fire/smoke detection, the AHU smoke<br />
detectors shall be used to alarm the DDC system. The AHU supply and<br />
return fans will run continuously but the outside air dampers shall be closed<br />
by occupancy sensors, carbon dioxide controls, or by the EMS during<br />
unoccupied mode. If smoke enters an AHU, the fans in that AHU shall stop;<br />
however all other fans in the building shall continue to run if allowed by<br />
code.<br />
r) Where perimeter heat is needed at large windows and exterior walls, it shall<br />
be interlocked with AHU/zone control. Perimeter heat will normally be<br />
supplied from a closed building LTHW loop with a converter served by the<br />
<strong>University</strong> MTHW system.<br />
s) Freeze protection shall be provided on all air handling units. Freezestats<br />
shall stop the supply and return fans, close the outside damper, and open<br />
the heating coil valve. Where DDC is used, the freezestat controls shall be<br />
completely independent <strong>of</strong> the DDC system.<br />
t) Blender sections shall be provided on all AHUs other than single pass units<br />
to ensure that the outside air and return air are adequately mixed.<br />
5) Identification<br />
a) All piping and equipment in mechanical equipment rooms and central plants<br />
shall be completely painted according to the “Scheme for the Identification<br />
<strong>of</strong> Piping Systems”, ANSI A13.1 and the “Safety Code Color for Marking<br />
Physical Hazards”, ANSI Z53.1, latest revisions.<br />
b) All piping in buildings shall be identified by means <strong>of</strong> alphabetical stencils<br />
and color codes, showing contents <strong>of</strong> the piping and the direction <strong>of</strong> flow.<br />
Piping shall be identified at 30’ intervals, on both sides <strong>of</strong> penetrations<br />
through walls and floors, and at each directional change.<br />
c) All valves shall also be identified with stamped brass tags or discs secured<br />
with non-ferrous beaded chain. Valve numbers shall be engraved or<br />
stamped as large as possible on tags (1 inch by 2 inches) or discs (1.25 inch<br />
diameter) attached to the valves by 10-gauge brass "s" hooks. Provide a<br />
framed valve schedule in mechanical rooms.<br />
d) All motor driven equipment, HVAC components, and major electrical boxes<br />
shall be individually numbered on the drawings by the A/E and have<br />
corresponding number plates on the equipment. (Example: For unit<br />
heaters, use UH-1, UH-2, etc., even though both units are <strong>of</strong> the same size<br />
and type.) All designations shall be integrated with and distinguished from<br />
existing designations.<br />
BSRV 4 HEATING, VENTILATION, AND AIR CONDITIONING 179