26.10.2013 Views

Facility Design Guidelines - Facilities Management - University of ...

Facility Design Guidelines - Facilities Management - University of ...

Facility Design Guidelines - Facilities Management - University of ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

ecirculating systems shall have a means to pre-cool and dehumidify outside<br />

air before being mixed with the return air rather than cooling the entire<br />

supply airstream to dehumidify and then reheating. A chilled water coil,<br />

heat recovery device or other method approved by <strong>Facilities</strong> <strong>Management</strong><br />

may be used.<br />

o) Sequence will specify if fans run continuously or can be shut <strong>of</strong>f. Supply,<br />

return, and exhaust fans shall be interlocked as required.<br />

p) AHUs should have manual override to run unit with high outside airflow (for<br />

venting odors from new carpet/furniture, floods, etc.)<br />

q) In buildings that do not have other fire/smoke detection, the AHU smoke<br />

detectors shall be used to alarm the DDC system. The AHU supply and<br />

return fans will run continuously but the outside air dampers shall be closed<br />

by occupancy sensors, carbon dioxide controls, or by the EMS during<br />

unoccupied mode. If smoke enters an AHU, the fans in that AHU shall stop;<br />

however all other fans in the building shall continue to run if allowed by<br />

code.<br />

r) Where perimeter heat is needed at large windows and exterior walls, it shall<br />

be interlocked with AHU/zone control. Perimeter heat will normally be<br />

supplied from a closed building LTHW loop with a converter served by the<br />

<strong>University</strong> MTHW system.<br />

s) Freeze protection shall be provided on all air handling units. Freezestats<br />

shall stop the supply and return fans, close the outside damper, and open<br />

the heating coil valve. Where DDC is used, the freezestat controls shall be<br />

completely independent <strong>of</strong> the DDC system.<br />

t) Blender sections shall be provided on all AHUs other than single pass units<br />

to ensure that the outside air and return air are adequately mixed.<br />

5) Identification<br />

a) All piping and equipment in mechanical equipment rooms and central plants<br />

shall be completely painted according to the “Scheme for the Identification<br />

<strong>of</strong> Piping Systems”, ANSI A13.1 and the “Safety Code Color for Marking<br />

Physical Hazards”, ANSI Z53.1, latest revisions.<br />

b) All piping in buildings shall be identified by means <strong>of</strong> alphabetical stencils<br />

and color codes, showing contents <strong>of</strong> the piping and the direction <strong>of</strong> flow.<br />

Piping shall be identified at 30’ intervals, on both sides <strong>of</strong> penetrations<br />

through walls and floors, and at each directional change.<br />

c) All valves shall also be identified with stamped brass tags or discs secured<br />

with non-ferrous beaded chain. Valve numbers shall be engraved or<br />

stamped as large as possible on tags (1 inch by 2 inches) or discs (1.25 inch<br />

diameter) attached to the valves by 10-gauge brass "s" hooks. Provide a<br />

framed valve schedule in mechanical rooms.<br />

d) All motor driven equipment, HVAC components, and major electrical boxes<br />

shall be individually numbered on the drawings by the A/E and have<br />

corresponding number plates on the equipment. (Example: For unit<br />

heaters, use UH-1, UH-2, etc., even though both units are <strong>of</strong> the same size<br />

and type.) All designations shall be integrated with and distinguished from<br />

existing designations.<br />

BSRV 4 HEATING, VENTILATION, AND AIR CONDITIONING 179

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!