26.10.2013 Views

Facility Design Guidelines - Facilities Management - University of ...

Facility Design Guidelines - Facilities Management - University of ...

Facility Design Guidelines - Facilities Management - University of ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

(LFMC) not exceeding 6 feet in length shall be used only for connections to motors or<br />

equipment subject to movement or vibration. Exceptions may be granted for renovation<br />

projects allowing over 6’ <strong>of</strong> flexible conduit where 1) in location that are not accessible<br />

2) for the connection <strong>of</strong> light fixtures provided they have an insulated ground wire sized<br />

in accordance with NEC 3) Other special circumstance with prior approval from OUBO<br />

electrical engineer. Flexible conduit may also be used for connections to systems<br />

furniture and under floor power requirements for computer server room applications.<br />

All wiring shall be run in EMT conduit, surface metal raceway or cable tray. EMT conduit<br />

from the communications or power or control wiring (under 50V) wall outlet box may<br />

terminate several inches above the ceiling where lay-in ceiling tile is used. Cabling above<br />

the ceiling shall be neatly bundled and attached to or independently supported from the<br />

building structure above. Wiring, conduit or cable shall not be laid on the ceiling system<br />

or attached to the ceiling suspension wire. Support from the building structure.<br />

All empty conduits shall have a 65-lb test polymer (or equivalent) pull string tied <strong>of</strong>f at<br />

both ends. All conduits shall be concealed in finished areas. Surface mounted raceways<br />

may be used for horizontal distribution <strong>of</strong> electrical and data cabling in computer rooms,<br />

computer classrooms and research laboratories. Pre-existing conditions <strong>of</strong> surface<br />

mounted wiring and conduit does not constitute permission to add surface mounted<br />

hardware and raceway.<br />

Conductors:<br />

BSRV 6.2.6 DEVICES<br />

All conductors shall be copper with 75 °C insulation or better. All power and lighting<br />

circuit conductors shall be #12 AWG or larger. #8 AWG and larger shall be stranded<br />

conductors and #10 AWG and smaller shall be solid conductors. Minimum control wires<br />

shall be #14 AWG and minimum signal wire no smaller than #18 AWG unless otherwise<br />

recommended by manufacturer.<br />

All new circuits shall have a green equipment-grounding conductor sized per NEC Article<br />

250. All new electrical equipment such as switchboards, transformers and generators<br />

shall have grounding conductor sized per NEC Article 250.<br />

No more than three single phase circuits or eight (8) current-carrying conductors shall<br />

be run in a single conduit.<br />

Ground fault circuit interrupter outlets or breakers are required on all power outlets<br />

within 6-feet <strong>of</strong> water sources. Where the presence <strong>of</strong> water or grounded surfaces<br />

contribute to a hazardous environment, ground fault protection is required.<br />

All devices shall be 20A, heavy-duty specification (minimum) grade devices. Residential<br />

grade devices are not permitted.<br />

Receptacles shall be mounted with the ground pole in the UP position unless otherwise<br />

directed.<br />

Health system requirements:<br />

BSRV 6 ELECTRICAL SYSTEMS 218

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!