BE 2 SUPERSTRUCTURE<br />

BE 2.1 GEOTECHNICAL DESIGN; EARTH PRESSURE LATERAL LOADS<br />

BE 2.1.1 BUILDING FRAME DESIGN<br />

Building framing shall be designed to resist Earth Pressure Lateral Loads internally.<br />

Assumption shall be that the excavation support systems shall facilitate below grade<br />

building construction, but in the long term may transfer partial or all Earth Pressure<br />

Lateral Loads to building frame designed to resist it internally.<br />

BE 2.1.2 GLOBAL STABILITY<br />

In situations <strong>of</strong> unbalanced Earth Pressure Lateral Loads against a building/structure,<br />

calculations shall be performed to verify Global stability <strong>of</strong> excavation at critical stages<br />

<strong>of</strong> construction, whether excavation support systems are used or not, and for the<br />

completed building/structure condition after final grading.<br />

BE 2.2 FLOOR AND ROOF CONSTRUCTION<br />

Structural framing for research laboratories, and other uses where instrumentation is<br />

sensitive to building vibration, shall be designed for resistance <strong>of</strong> vibration. The Basis <strong>of</strong><br />

<strong>Design</strong> Narrative shall establish vibration criteria in the Preliminary <strong>Design</strong> to be<br />

reflected in structural calculations and construction details.<br />

Structures requiring design compatibility with magnetically and electrically sensitive<br />

equipment in research and medical facilities shall be demonstrated to have structural<br />

materials and techniques compatible with such identified or commonly used<br />

equipment.<br />

BE 2.3 BEARING CONNECTIONS<br />

Use “N” Bearing Type Connections (unless required otherwise) for framed connections<br />

with 2 bolts minimum.<br />

BE 2.4 ADDITION OF LOADS TO EXISTING STRUCTURES<br />

Prior to mounting any antennae, microwave dishes, HVAC equipment or other items on<br />

the ro<strong>of</strong> <strong>of</strong> an existing building, the adequacy <strong>of</strong> the structural framing to support the<br />

additional live, dead, wind and lateral loads shall be checked by a licensed Structural<br />

Engineer. Consideration must be given to deflection from the added load(s), to<br />

potential for vibration, to potential for ponding water, and to the consequences <strong>of</strong><br />

overturning moments on stressed attachments and construction.<br />

BE 2 SUPERSTRUCTURE 116