Mounting<br />

Soft starter ventilation<br />

On soft starters installed with a cooling fan, the fan is factory set to switch on automatically as soon as the heatsink temperature reaches<br />

46°C (114.8°F).<br />

It is switched off when the heatsink temperature falls back to 43°C (109.4°F). This behavior can be mo dified by adjusting the FAn parameter<br />

in IO menu on page 61.<br />

Fan flow rates<br />

(1)Cubic Feet / Minute<br />

Mounting in a General Purpose Metal Enclosure<br />

Observe the mounting recommendations on the previous page.<br />

To help proper air circulation in the soft starter:<br />

• Install ventilation grilles.<br />

• Verify that ventilation is adequate: if not install a forced ventilation unit, with a<br />

filter if necessary.<br />

Derate the soft starter current IcL by 2.2% per °C for temperatures above 40°C up to<br />

60°C (104°F up to 140°F).<br />

18<br />

Reference Frame<br />

size<br />

Unit Standard With optional fan kit<br />

110 V 230 V 110 V 230 V<br />

SH31-7.5, 15.0, 22.0 A m 3 /hour - - 28 31<br />

CFM (1) - - 16 18<br />

SH31-30.0, 37.0, 45.0 B m 3 /hour - - 28 31<br />

CFM (1) - - 16 18<br />

SH31- 55.0, 75.0, 90.0 C m 3 /hour - - 108 108<br />

CFM (1) - - 64 64<br />

SH31-110, 132, 160, 200 D m 3 /hour 148 148 - -<br />

CFM (1) 87 87 - -<br />

SH31-250, 315 E m 3 /hour 148 148 - -<br />

CFM (1) 87 87 - -