Wiring<br />
The SH31-.../4 range (230-440 V) can be connected in the motor supply line or inside delta connection of the motor.<br />
The SH31 in line connection<br />
The motor connection depends on the supply voltage. Two possibilities are shown below: star connection and delta connection.<br />
The SH31 connected inside delta connection<br />
30<br />
SH31<br />
Motor<br />
Star connection Delta connection<br />
SH31<br />
Motor<br />
CAUTION<br />
RISK OF DAMAGE TO THE SOFT STARTER<br />
• Only the SH31-.../4 range can be installed inside delta connection.<br />
• Ensure connection exactly as shown on the example.<br />
• Line voltage should not exceed 440 V.<br />
• The parameter dLtA must be set to dLt.<br />
Failure to follow these instructions can result in equipment damage.<br />
Note: Phase sequence must be 1 - 2 - 3