Wiring<br />

The SH31-.../4 range (230-440 V) can be connected in the motor supply line or inside delta connection of the motor.<br />

The SH31 in line connection<br />

The motor connection depends on the supply voltage. Two possibilities are shown below: star connection and delta connection.<br />

The SH31 connected inside delta connection<br />

30<br />

SH31<br />

Motor<br />

Star connection Delta connection<br />

SH31<br />

Motor<br />

CAUTION<br />

RISK OF DAMAGE TO THE SOFT STARTER<br />

• Only the SH31-.../4 range can be installed inside delta connection.<br />

• Ensure connection exactly as shown on the example.<br />

• Line voltage should not exceed 440 V.<br />

• The parameter dLtA must be set to dLt.<br />

Failure to follow these instructions can result in equipment damage.<br />

Note: Phase sequence must be 1 - 2 - 3