Advanced protections menu (PrO)<br />
(1)Only available when Advanced mode LAC page 50 is set to On.<br />
(2)Only available by Modbus.<br />
58<br />
Code Name/Description R/W Adjustment range Factory setting<br />
PrO (1) Advanced protections menu (continued)<br />
PHL • Phase loss detection R/W* On<br />
On<br />
oFF<br />
Manage the input (or line) phase loss controls.<br />
- on<br />
- off<br />
Note: Trip message is PHF.<br />
USd • Under voltage threshold R/W 50..90 (% of ULn) 70%<br />
Trips the soft starter when the voltage drops below the set level for a time longer than under voltage time delay<br />
(USt).<br />
Line voltage (V)<br />
Note:<br />
Becomes operational only after start signal. When voltage drops to zero (voltage outage), the soft starter will trip<br />
immediately, overriding the delay. Trip message is USF.<br />
USt • Under voltage time delay R/W 1..10 5 s<br />
Adjusts the time of under voltage threshold USd.<br />
Time<br />
(s)