Advanced protections menu (PrO)<br />

(1)Only available when Advanced mode LAC page 50 is set to On.<br />

(2)Only available by Modbus.<br />

58<br />

Code Name/Description R/W Adjustment range Factory setting<br />

PrO (1) Advanced protections menu (continued)<br />

PHL • Phase loss detection R/W* On<br />

On<br />

oFF<br />

Manage the input (or line) phase loss controls.<br />

- on<br />

- off<br />

Note: Trip message is PHF.<br />

USd • Under voltage threshold R/W 50..90 (% of ULn) 70%<br />

Trips the soft starter when the voltage drops below the set level for a time longer than under voltage time delay<br />

(USt).<br />

Line voltage (V)<br />

Note:<br />

Becomes operational only after start signal. When voltage drops to zero (voltage outage), the soft starter will trip<br />

immediately, overriding the delay. Trip message is USF.<br />

USt • Under voltage time delay R/W 1..10 5 s<br />

Adjusts the time of under voltage threshold USd.<br />

Time<br />