Utility menu (UtIL)<br />

*: Write only when the soft starter is stopped<br />

(1) Accessible, except motor in run state, using the key shortcut<br />

64<br />

Code Name/Description R/W Adjustment range Factory setting<br />

UtIL (1) Utility menu<br />

tESt • Soft starter self test R/W* On oFF<br />

Result<br />

Good<br />

BAd. Possible causes :<br />

- Improper internal voltage,<br />

- Checksum error,<br />

- Disconnected keyboard,<br />

- Disconnected heatsink thermal sensor,<br />

- Disconnected bypass relay (frame size C).<br />

If the detected fault persists, contact BLEMO product support.<br />

UdP • Soft starter software version R 0000..9999<br />

Two first digits: version<br />

Two last digits: sub version<br />

FCS • Back to factory settings R/W*<br />

UNINTENDED EQUIPMENT OPERATION<br />

<strong>DANGER</strong><br />

Check that the modification of the current configuration is compatible with the wiring diagram used.<br />

Failure to follow these instructions will result in death or serious injury.<br />

After press "Enter", SUrE is displayed. After press "Enter", parameters go back to factory settings.<br />

rPr • Reset of trip history and counters R/W*<br />

ESC +<br />

After press "Enter", SUrE is displayed. After press "Enter", trip history and counters are reset (rnt, dEF1 to dEF9<br />