Utility menu (UtIL)<br />
*: Write only when the soft starter is stopped<br />
(1) Accessible, except motor in run state, using the key shortcut<br />
64<br />
Code Name/Description R/W Adjustment range Factory setting<br />
UtIL (1) Utility menu<br />
tESt • Soft starter self test R/W* On oFF<br />
Result<br />
Good<br />
BAd. Possible causes :<br />
- Improper internal voltage,<br />
- Checksum error,<br />
- Disconnected keyboard,<br />
- Disconnected heatsink thermal sensor,<br />
- Disconnected bypass relay (frame size C).<br />
If the detected fault persists, contact BLEMO product support.<br />
UdP • Soft starter software version R 0000..9999<br />
Two first digits: version<br />
Two last digits: sub version<br />
FCS • Back to factory settings R/W*<br />
UNINTENDED EQUIPMENT OPERATION<br />
<strong>DANGER</strong><br />
Check that the modification of the current configuration is compatible with the wiring diagram used.<br />
Failure to follow these instructions will result in death or serious injury.<br />
After press "Enter", SUrE is displayed. After press "Enter", parameters go back to factory settings.<br />
rPr • Reset of trip history and counters R/W*<br />
ESC +<br />
After press "Enter", SUrE is displayed. After press "Enter", trip history and counters are reset (rnt, dEF1 to dEF9<br />
in the SUP menu).