Advanced communication menu (COP)<br />
(1)Only available when Advanced mode LAC page 50 is set to On.<br />
*: Write only when the soft starter is stopped.<br />
62<br />
Code Name/Description R/W Adjustment range Factory setting<br />
COP Advanced communication menu<br />
Add • Modbus address R/W* 1..247 oFF<br />
oFF<br />
1 to 247<br />
- off<br />
- Modbus address<br />
Note: the modification will be taken into account only at the next control power on.<br />
tbr • Modbus baudrate R/W* 4.8, 9.6, 19.2 Kbps 19.2 Kbps<br />
Note: the modification will be taken into account only at the next control power on.<br />
With the remote keypad, set 19.2 Kbps<br />
For • Modbus format R/W* 8E1<br />
8o1<br />
8E1<br />
8n1<br />
8n2<br />
- 8 bit, odd parity, 1 stop bit<br />
- 8 bit, even parity, 1 stop bit<br />
- 8 bit, no parity, 1 stop bit<br />
- 8 bit, no parity, 2 stop bit<br />
Note: the modification will be taken into account only at the next control power on.<br />
With the remote keypad, set 8E1<br />
ttO • Modbus time out<br />
Note: 0.1s on keypad becomes 1 with Modbus (1/10th s value with Modbus).<br />
Trip message is SLF.<br />
LOSS OF CONTROL<br />
WARNING<br />
R/W* 0.1..60.0 s 5.0 s<br />
Check that the selection of Modbus time out will not endanger personnel or equipment in any way.<br />
Failure to follow this instruction can result in death or serious injury or equipment damage.<br />
CtrL • Command channel R/W* LCL<br />
LCL<br />
dbS<br />
- local command: with the control terminals<br />
- remote command: Modbus<br />
Note: During soft start and soft stop, parameters values written by Modbus are not taken into account.<br />
LI1 must be activated (LI1 = 1) to allow the remote command.