Advanced adjustments menu (AdJ)<br />
Code Name/Description R/W Adjustment range Factory setting<br />
AdJ (1) Advanced adjustments menu<br />
Snb • Number of starts R/W oFF, 1..10 oFF<br />
Limiting the number of soft starts and soft stops during an adjustable period of time. This period is set with SLG.<br />
When the number of soft starts and soft stops is above the Snb value, during SLG period, the trip message is SnbF<br />
or tbS.<br />
Example 1: Snb = 6, SLG = 30 min and dEC = Free<br />
6 starts are allowed in 30 min period. If you do 7 starts, you will have SnbF trip message.<br />
Example 2: Snb = 6, SLG = 30 min and dEC = 10<br />
3 starts and 3 stops are allowed in 30 min period. If you do 4 starts, you will have SnbF trip message.<br />
SLG • Starts period<br />
See Snb above.<br />
bSt • Boost time<br />
(1)Only available when Advanced mode LAC page 50 is set to On.<br />
*: Write only when the soft starter is stopped<br />
R/W 1..60 min 30 min<br />
R/W 0.0 .. 1.0<br />
by increment of 0.1<br />
0 (no pulse)<br />
Intended to start high friction loads that require high starting torque for a short time.<br />
A pulse of 80% Uln, without current limit, is initiated to break the load free. Pulse duration is adjustable, 0.1 – 1sec.<br />
After this pulse, the voltage is ramped down to the initial voltage setting, before ramping up again to full voltage<br />
according to start parameters settings.<br />
Voltage %<br />
Run 0.1 to 1s<br />
Note: bSt is inactive (=0) when dLtA = dLt. In this case, bSt value is not used<br />
and is not relevant.<br />
0.1 s on keypad becomes 1 with Modbus (1/10th s value with Modbus).<br />
Time (s)<br />