Advanced adjustments menu (AdJ)<br />

Code Name/Description R/W Adjustment range Factory setting<br />

AdJ (1) Advanced adjustments menu<br />

Snb • Number of starts R/W oFF, 1..10 oFF<br />

Limiting the number of soft starts and soft stops during an adjustable period of time. This period is set with SLG.<br />

When the number of soft starts and soft stops is above the Snb value, during SLG period, the trip message is SnbF<br />

or tbS.<br />

Example 1: Snb = 6, SLG = 30 min and dEC = Free<br />

6 starts are allowed in 30 min period. If you do 7 starts, you will have SnbF trip message.<br />

Example 2: Snb = 6, SLG = 30 min and dEC = 10<br />

3 starts and 3 stops are allowed in 30 min period. If you do 4 starts, you will have SnbF trip message.<br />

SLG • Starts period<br />

See Snb above.<br />

bSt • Boost time<br />

(1)Only available when Advanced mode LAC page 50 is set to On.<br />

*: Write only when the soft starter is stopped<br />

R/W 1..60 min 30 min<br />

R/W 0.0 .. 1.0<br />

by increment of 0.1<br />

0 (no pulse)<br />

Intended to start high friction loads that require high starting torque for a short time.<br />

A pulse of 80% Uln, without current limit, is initiated to break the load free. Pulse duration is adjustable, 0.1 – 1sec.<br />

After this pulse, the voltage is ramped down to the initial voltage setting, before ramping up again to full voltage<br />

according to start parameters settings.<br />

Voltage %<br />

Run 0.1 to 1s<br />

Note: bSt is inactive (=0) when dLtA = dLt. In this case, bSt value is not used<br />

and is not relevant.<br />

0.1 s on keypad becomes 1 with Modbus (1/10th s value with Modbus).<br />

Time (s)<br />

53