Wiring<br />
Installation Precautions<br />
Good wiring practice requires the separation of control circuit wiring from all power (line and load) wiring. Power wiring to the motor must<br />
have the maximum possible separation from all other power wiring. Do not run them in the same conduit. This separation reduces the<br />
possibility of coupling electrical noise between circuits.<br />
Follow these precautions when installing the SH31 soft starter:<br />
• Voltage and frequency specifications for the input line must match the soft starter configuration.<br />
• A disconnect switch must be installed between the input line and the soft starter.<br />
26<br />
<strong>DANGER</strong><br />
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH<br />
• Read and understand this manual before installing or operating the SH31. Installation, adjustment, repair, and maintenance must be<br />
performed by qualified personnel.<br />
• The user is responsible for compliance with all international and national electrical code requirements with respect to grounding of<br />
all equipment.<br />
• Many parts of this soft starter, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH. Use only electrically<br />
insulated tools.<br />
• DO NOT touch unshielded components or terminal strip screw connections with voltage present.<br />
• Before servicing the soft starter:<br />
- Disconnect all power, including external control power that may be present.<br />
- Place a “DO NOT TURN ON” label on all power disconnects.<br />
- Lock all power disconnects in the open position.<br />
• Install and close all covers before applying power or starting and stopping the soft starter.<br />
Failure to follow these instructions will result in death or serious injury.<br />
<strong>DANGER</strong><br />
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH<br />
• The solid state switches of the SH31 soft starter’s power circuit do not provide complete isolation from the AC line. Due to leakage<br />
currents through the solid-state switches, hazardous voltages can be present on the soft starter load-side power circuit whenever<br />
power is applied to the line side of the soft starter.<br />
• Disconnect all power before servicing the soft starter or motor.<br />
Failure to follow these instructions will result in death or serious injury.<br />
• When using an isolation contactor, the contactor must close before or at the same time as the application of the soft starter run<br />
command. If line power is not detected at the L1, L2, and L3 terminals of the soft starter within 500 ms of this run command, a Phase<br />
Failure trip will occur.<br />
• External overcurrent protection devices (OCPD), either fuses or a circuit breaker, must be installed on the line-side connections of<br />
the SH31 soft starter. The maximum recommended OCPD rating, along with the associated soft starter short circuit withstand rating,<br />
is listed on page 84.