Settings menu (SEt)<br />

52<br />

Code Name/Description R/W Adjustment range Factory setting<br />

SEt Settings menu (continued)<br />

ACC • Acceleration time R/W 1..60 s 10 s<br />

Determines motor’s voltage ramp up time, if SSC is set to OFF.<br />

Determines motor’s torque ramp up time, if SSC is set to ON.<br />

Run command<br />

dEC • Deceleration time R/W FrEE, 1...60 s Free<br />

1 to 60<br />

FrEE<br />

Determines motor’s voltage ramp down time, if SSC is set to OFF.<br />

Determines motor’s torque ramp down time, if SSC is set to ON.<br />

- Deceleration time<br />

- Freewheel deceleration<br />

%<br />

Run<br />

EdC • End of deceleration<br />

Time(s)<br />

R/W 0..10 0<br />

Threshold for changing to freewheel stop mode at the end of deceleration.<br />

Soft deceleration will end when the estimated torque falls below the EdC value.<br />

Note: Edc is inactive when dLtA = dLt. In this case, EdC value is not used and is not relevant.<br />

Motor<br />

voltage<br />

tHP • Motor thermal protection<br />

10<br />

20<br />

30<br />

dEC<br />

Freewheel<br />

Time(s)<br />

Motor<br />

voltage<br />

R/W 10<br />

To select the class of motor thermal protection, see explanations and curves page 22.<br />

- IEC class 10<br />

- IEC class 20<br />

- IEC class 30 (heavy duty)<br />

Note: To activate the Motor thermal protection, set ItH to ErUn or On, page 59<br />

Freewheel