Advanced settings menu (SEt2)<br />

Code Name/Description R/W Adjustment range Factory setting<br />

SEt2 (1) Advanced settings menu<br />

SEt2 allows you to have a 2nd set for the 5 parameters below.<br />

These parameters have the same definition as SEt.<br />

They can be validated with 2 possibilities:<br />

• Remotely by communication.<br />

• With logic input.<br />

t92 • 2nd initial voltage R/W 10..50 % of full voltage<br />

Uln, by increment of 5<br />

Same as Initial voltage t90 page 51.<br />

ILt2 • 2nd current limit<br />

Same as Current limit ILt page 51.<br />

(1)Only available when Advanced mode LAC page 50 is set to On.<br />

R/W 200..700 of In2 with max<br />

350% IcL<br />

ACC2 • 2nd acceleration time R/W 1..60 s 10 s<br />

Same as acceleration time ACC page 52.<br />

dEC2 • 2nd deceleration time R/W FrEE, 1..60 s FrEE<br />

Same as deceleration time dEC page 52.<br />

In2 • 2nd motor rated Current<br />

Same as motor rated current In page 50.<br />

30%<br />

350%<br />

R/W* 0.4 IcL up to IcL According to the soft<br />

starter rating (see<br />

pages 11 to 22)<br />