Advanced protections menu (PrO)<br />

Code Name/Description R/W Adjustment range Factory setting<br />

PrO (1) Advanced protections menu (continued)<br />

OSd • Over voltage threshold R/W* 110..125% of Uln 120%<br />

Trips the soft starter when mains voltage increases above the set level for a time longer than over voltage time<br />

delay (OSt).<br />

Line voltage (V)<br />

(1)Only available when Advanced mode LAC page 50 is set to On.<br />

*: Write only when the soft starter is stopped<br />

Time<br />

(s)<br />

Note: Trip message is OSF. The trip appears only after a Run command.<br />

OSt • Over voltage time delay R/W 1..10 2 s<br />

Trips the soft starter when mains voltage increases above the set level for a time longer than overvolt delay.<br />

Note: Trip message is OSF.<br />

PtC • PTC probes motor monitoring R/W oFF<br />

oFF<br />

On<br />

The PTC probes on the motor must be connected to the correct analog input (see page 25).<br />

This protection is independent of the Motor thermal protection tHP.<br />

Both types of protection can be used simultaneously.<br />

- off (No PTC probes are not activated)<br />

- on (PTC probes activated. Wire the probes)<br />

Note: Trip message is OtF.<br />

ItH • Overload protection R/W* On<br />

oFF<br />

ErUn<br />

On<br />

ItH determines if and when the overload protection is active<br />

- off: the overload protection is disabled<br />

- Erun: the overload protection is enable only during the steady state (rUn)<br />

- On: the overload protection is always enable.<br />

Note: Trip message is OLF.ItH set to oFF resets the thermal state of the motor when the soft starter is stopped.<br />

CAUTION<br />

RISK OF DAMAGE TO THE SOFT STARTER AND THE MOTOR<br />

• When ItH = oFF, it is recommended to use PtC probes to protect the motor against overheating.<br />

• When ItH = ErUn, it is recommended to set tLS to the maximum start time of the installation, to protect the<br />

installation in case of motor stalling.<br />

Failure to follow these instructions can result in equipment damage.<br />