Advanced protections menu (PrO)<br />
Code Name/Description R/W Adjustment range Factory setting<br />
PrO (1) Advanced protections menu (continued)<br />
OSd • Over voltage threshold R/W* 110..125% of Uln 120%<br />
Trips the soft starter when mains voltage increases above the set level for a time longer than over voltage time<br />
delay (OSt).<br />
Line voltage (V)<br />
(1)Only available when Advanced mode LAC page 50 is set to On.<br />
*: Write only when the soft starter is stopped<br />
Time<br />
(s)<br />
Note: Trip message is OSF. The trip appears only after a Run command.<br />
OSt • Over voltage time delay R/W 1..10 2 s<br />
Trips the soft starter when mains voltage increases above the set level for a time longer than overvolt delay.<br />
Note: Trip message is OSF.<br />
PtC • PTC probes motor monitoring R/W oFF<br />
oFF<br />
On<br />
The PTC probes on the motor must be connected to the correct analog input (see page 25).<br />
This protection is independent of the Motor thermal protection tHP.<br />
Both types of protection can be used simultaneously.<br />
- off (No PTC probes are not activated)<br />
- on (PTC probes activated. Wire the probes)<br />
Note: Trip message is OtF.<br />
ItH • Overload protection R/W* On<br />
oFF<br />
ErUn<br />
On<br />
ItH determines if and when the overload protection is active<br />
- off: the overload protection is disabled<br />
- Erun: the overload protection is enable only during the steady state (rUn)<br />
- On: the overload protection is always enable.<br />
Note: Trip message is OLF.ItH set to oFF resets the thermal state of the motor when the soft starter is stopped.<br />
CAUTION<br />
RISK OF DAMAGE TO THE SOFT STARTER AND THE MOTOR<br />
• When ItH = oFF, it is recommended to use PtC probes to protect the motor against overheating.<br />
• When ItH = ErUn, it is recommended to set tLS to the maximum start time of the installation, to protect the<br />
installation in case of motor stalling.<br />
Failure to follow these instructions can result in equipment damage.<br />
59